| 2008-04-22 13:37:56 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. PERMIT APPLICATION STATES "RENEWAL OF PERMIT CLOSED |
| | 05061640 INSTALL U/G 500 LD TANK W/INTERIOR EXTERIOR |
| | GAS LINES INSTALL WTR/HTR. ALL OTHER APPLIANCES". |
| | NOTE: THERE IS NO SUCH THING AS A RENEWAL OF A CLOSED |
| | PERMIT. PERMIT NUMBER 05061640 WAS CLOSED 2/21/06 THIS |
| | IS A NEW GAS PERMIT APPLICATION AND AS THE PERMIT |
| | APPLICATION STATES "DESCRIBE PROJECT IN DETAIL (FAILURE |
| | TO DO SO MAY RESULT IN DELAYS) THE SUBMITTED PERMIT |
| | APPLICATION DOES NOT DO THIS. WHAT IS A LD TANK, |
| | SHOULDN'T THIS BE A LP TANK? ALSO THE LP TANK IS |
| | EXISTING AND DOES NOT NEED TO BE ON THE PERMIT |
| | APPLICATION. PLEASE CLEARLY INDICATE ONLY THE PROPOSED |
| | WORK ON THE PERMIT APPLICATION AND CORRELATE THE PLANS |
| | TO REFLECT THE APPLICATION. PER (W.P.B. AS AMENDED) |
| | SECTION 105 PERMITS AND FBC FUEL GAS SECTION 401.1 |
| | SCOPE. |
| | |
| | 2. REMOVE THE RED LETTERED WORD "REVISION" FROM THE |
| | RESUBMITTED PLANS. THIS IS NOT A REVISION. THIS IS A |
| | NEW GAS PERMIT APPLICATION. PLEASE REFERENCE COMMENT |
| | NUMBER 1. PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS AND FBC FUEL GAS |
| | SECTION 401.1 SCOPE. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |