2008-04-22 09:14:39GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. NOT ALL CORRESPONDING LENGTH ARE INDICATED FOR ALL
 CUT SECTIONS OF PIPE. REFERENCE THE RED CIRCLED YELLOW
 HIGH LIGHTED CUT SECTIONS AND COMPLY. PER FBC FUEL GAS
 SECTION 401.1 SCOPE.
  
 2. NOTE: THE LONGEST LENGTH OF 50' IS BEING INDICATED
 WRONG. THE ADDED SUM OF THE INDICATED CORRESPONDING
 LENGTHS OF CUT SECTIONS OF PIPE IS 50' HOWEVER THATS
 NOT ADDING WHAT IS BEING ASKED FOR IN COMMENT #1.
 PLEASE CORRECT AND COMPLY PER FBC FUEL GAS SECTION
 401.1 SCOPE.
  
 3. PLEASE PROVIDE THE PRINTED NAME OF THE PERSON
 TAKING RESPONSIBILITY FOR THE DRAWINGS. NOTE: ALL
 PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA BEING
 FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED NAME
 OF THE RESPONSIBLE PERSON WITH THE ORIGINAL SIGNATURE
 AND DATE ON SUCH INFORMATION. PER SECTION *106.3.4.3.
  
 4. NOTE: THE SUBMITTED MANUFACTURER SHEETS FOR THE GAS
 REFRIGERATOR/FREEZER ARE FOR PROPANE GAS HOWEVER THE
 SUBMITTED GAS DRAWINGS ARE INDICATING NATURAL GAS.
 PLEASE CLARIFY. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. VALUE FOR THE JOB IS TO LOW. JOB MUST INCLUDE THE
 PRICE OF THE GAS REFRIGERATOR/FREEZER. PLEASE SEE A
 COPY OF THE APPLIANCE PRICE FROM AN ONLINE SEARCH
 INDICATING THE PRICE AS $2363.00 ATTACHED TO THESE
 COMMENTS. PLEASE ADJUST THE VALUE AND PAY THE
 DIFFERENCE BEFORE RESUBMITTING.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]