| 2008-04-22 09:14:39 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. NOT ALL CORRESPONDING LENGTH ARE INDICATED FOR ALL |
| | CUT SECTIONS OF PIPE. REFERENCE THE RED CIRCLED YELLOW |
| | HIGH LIGHTED CUT SECTIONS AND COMPLY. PER FBC FUEL GAS |
| | SECTION 401.1 SCOPE. |
| | |
| | 2. NOTE: THE LONGEST LENGTH OF 50' IS BEING INDICATED |
| | WRONG. THE ADDED SUM OF THE INDICATED CORRESPONDING |
| | LENGTHS OF CUT SECTIONS OF PIPE IS 50' HOWEVER THATS |
| | NOT ADDING WHAT IS BEING ASKED FOR IN COMMENT #1. |
| | PLEASE CORRECT AND COMPLY PER FBC FUEL GAS SECTION |
| | 401.1 SCOPE. |
| | |
| | 3. PLEASE PROVIDE THE PRINTED NAME OF THE PERSON |
| | TAKING RESPONSIBILITY FOR THE DRAWINGS. NOTE: ALL |
| | PLANS, SPECIFICATIONS, AND ACCOMPANYING DATA BEING |
| | FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED NAME |
| | OF THE RESPONSIBLE PERSON WITH THE ORIGINAL SIGNATURE |
| | AND DATE ON SUCH INFORMATION. PER SECTION *106.3.4.3. |
| | |
| | 4. NOTE: THE SUBMITTED MANUFACTURER SHEETS FOR THE GAS |
| | REFRIGERATOR/FREEZER ARE FOR PROPANE GAS HOWEVER THE |
| | SUBMITTED GAS DRAWINGS ARE INDICATING NATURAL GAS. |
| | PLEASE CLARIFY. PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. VALUE FOR THE JOB IS TO LOW. JOB MUST INCLUDE THE |
| | PRICE OF THE GAS REFRIGERATOR/FREEZER. PLEASE SEE A |
| | COPY OF THE APPLIANCE PRICE FROM AN ONLINE SEARCH |
| | INDICATING THE PRICE AS $2363.00 ATTACHED TO THESE |
| | COMMENTS. PLEASE ADJUST THE VALUE AND PAY THE |
| | DIFFERENCE BEFORE RESUBMITTING. |
| | PER FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |