| Date |
Text |
| 2008-04-21 16:15:35 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PERMIT APPLICATION STATES "ADD LINE TO TANKLESS |
| | W-HTR. AND W-HTR". THIS DOES NOT MAKES ANY SENSE, |
| | PLEASE CLEARLY INDICATE AND CLARIFY WHAT THE SCOPE OF |
| | WORK IS ON THE GAS PERMIT APPLICATION. PER (W.P.B.) |
| | SECTION 105 PERMITS. |
| | |
| | 2. NOT ALL CORRESPONDING LENGTHS ARE INDICATED FOR ALL |
| | CUT SECTIONS OF PIPE. REFERENCE THE RED CIRCLED YELLOW |
| | HIGH LIGHTED CUT SECTIONS AND COMPLY. PER FBC FUEL GAS |
| | SECTION 401.1 SCOPE. |
| | |
| | 3. THE LONGEST LENGTH IS BEING INDICATED WRONG AS 40'. |
| | THE ADDED SUM OF THE INDICATED CORRESPONDING LENGTHS OF |
| | CUT SECTIONS OF PIPE IS 44'. AND THAT NOT ADDING WHAT |
| | IS BEING ASKED FOR IN COMMENT #1 AND THE GAS PIPING IS |
| | NOT SIZED RIGHT. PER FBC FUEL GAS SECTION 401.1 SCOPE |
| | AND TABLE 402.4(2). REFERENCE TABLE 402.4(2) ATTACHED |
| | TO THESE COMMENTS INDCATING THIS. |
| | |
| | 4. NOTE: THE SUBMITTED EXISTING GAS SYSTEM DOES NOT |
| | REFLECT THE CLOSED GAS PERMIT #07010575 WHICH WAS |
| | FINALED 6/4/07. THAT PERMIT HAD A POOL/HTR., LOG/SET, |
| | COOKTOP, BBQ GRILL, WATER/HTR AND COLUMN LIGHTS. PLEASE |
| | KNOW THAT PERMIT DID NOT HAVE A DRYER AND THE BBQ HAD A |
| | REVISION INDICATING IT AS A FUTURE APPLIANCE. PLEASE |
| | REFERENCE THE ATTACHED GAS PERMIT INFORMATION OF SAID |
| | ADDRESS INDICATING THIS. PLEASE CLEARLY INDICATE THE |
| | CORRECT EXISTING GAS SYSTEM'S BTU LOAD AND LONGEST |
| | LENGTH. PER (W.P.B.) SECTION 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS AND FBC FUEL GAS SECTION 401.1 |
| | SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |