Plan Review Notes
Plan Review Notes For Permit 08040541
Permit Number 08040541
Review Stop E
Sequence Number 2
Notes
Date Text
2008-05-21 15:59:34 
  
  
 REVISION DENIED
  
 1} THE REVISION SUBMITTED INDICATES A COMPLETE REWIRE
 OF THE UNIT, IF NOT DIFFERENTIATE NEW FROM EXISTING.
  
 2} THE VALUE MUST INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES PER 108.3 FBC AS AMENDED.ADJUST THE VALUE
 TO INCLUDE ALL ADDED WORK UNDER THIS REVISION AT THE
 PERMIT CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING.
  
 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SEE
 COUNTERTOP ADJACENT TO THE "REF/FRZ".\
  
 4} INDICATE IF THE FLOOR RECEPTACLE IN BEDROOM #2 IS
 NEW OR EXISTING. IF NEW THE FLOOR MUST BE X-RAYED PRIOR
 TO MAKING ANY CUTS AND AN ENGINEER MUST VERIFY THE
 INSTALLATION WILL NOT WEAKEN THE STRUCTURAL INTEGRITY
 OR RATING OF THE FLOOR. INDICATE HOW THIS OUTLET WILL
 BE FED, AND FROM WHERE.
  
 PROVIDE A WRITTEN RESPONSE, PROVIDE ONE COPY OF THE
 OLD PLANS WHEN RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718