| Plan Review Notes For Permit 08040541 |
| Permit Number |
08040541 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-05-21 15:59:34 | | | | | | | | | | REVISION DENIED | | | | | | 1} THE REVISION SUBMITTED INDICATES A COMPLETE REWIRE | | | OF THE UNIT, IF NOT DIFFERENTIATE NEW FROM EXISTING. | | | | | | 2} THE VALUE MUST INCLUDE THE TOTAL COST OF LABOR AND | | | MATERIAL. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES PER 108.3 FBC AS AMENDED.ADJUST THE VALUE | | | TO INCLUDE ALL ADDED WORK UNDER THIS REVISION AT THE | | | PERMIT CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES | | | PRIOR TO RESUBMITTING. | | | | | | 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SEE | | | COUNTERTOP ADJACENT TO THE "REF/FRZ".\ | | | | | | 4} INDICATE IF THE FLOOR RECEPTACLE IN BEDROOM #2 IS | | | NEW OR EXISTING. IF NEW THE FLOOR MUST BE X-RAYED PRIOR | | | TO MAKING ANY CUTS AND AN ENGINEER MUST VERIFY THE | | | INSTALLATION WILL NOT WEAKEN THE STRUCTURAL INTEGRITY | | | OR RATING OF THE FLOOR. INDICATE HOW THIS OUTLET WILL | | | BE FED, AND FROM WHERE. | | | | | | PROVIDE A WRITTEN RESPONSE, PROVIDE ONE COPY OF THE | | | OLD PLANS WHEN RESUBMITTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|