 PROVISOR:
 712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN
 APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM INSTALLED
 AND TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479,
 WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01
 INCH OF WATER. THE SYSTEM SHALL HAVE AN F RATING AND A
 T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE
 REQUIRED RATING OF THE FLOOR PENETRATED. PLEASE
 INDICATE THE UL ASSEMBLY NUMBER FOR THE FLOOR
 PENETRATION WHERE THE PLUMBING PIPES WILL BE REMOVED
 AND CAPED. WHERE ANY PIPES ARE REMOVED FROM THE FLOOR
 CEILING/ASSEMBLY, THE HOLES SHALL BE SEALED WITH A UL
 ASSEMBLY WHICH SHALL MAINTAIN THE FLOOR RATING.