| Plan Review Notes For Permit 08040541 |
| Permit Number |
08040541 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-05-05 12:29:04 | | | | PROVISOR: | | | 712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN | | | APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM INSTALLED | | | AND TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, | | | WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 | | | INCH OF WATER. THE SYSTEM SHALL HAVE AN F RATING AND A | | | T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE | | | REQUIRED RATING OF THE FLOOR PENETRATED. PLEASE | | | INDICATE THE UL ASSEMBLY NUMBER FOR THE FLOOR | | | PENETRATION WHERE THE PLUMBING PIPES WILL BE REMOVED | | | AND CAPED. WHERE ANY PIPES ARE REMOVED FROM THE FLOOR | | | CEILING/ASSEMBLY, THE HOLES SHALL BE SEALED WITH A UL | | | ASSEMBLY WHICH SHALL MAINTAIN THE FLOOR RATING. |
|