| 2008-04-29 13:00:23 | BUILDING PLAN REVIEW |
| | PERMIT: 08040541 |
| | ADD: 1900 CONSULATE PLACE #406 |
| | CONT: SAARI CONSTRUCTION INC. |
| | TEL: (561)588-0720 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 4-29-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2)2004 FBC EXISTING |
| | 301.5 THE DESIGN PROFESSIONAL OR AN OWNER MUST ELECT |
| | ONE OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT |
| | TO SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 3)THE CONTRACTOR ON THE PERMIT APPLICATION IS A CBC |
| | CONTRACTOR WHO IS NOT ALLOWED TO DO ANY WORK PERTAINING |
| | TO THE STRUCTURAL WALLS OF THE BUILDING. A CERTIFIED |
| | GENERAL CONTRACTOR OR A CERTIFIED FIREPROOFING COMPANY |
| | SHALL APPLY FOR A SEPARATE APPLICATION TO SEAL ALL |
| | FLOOR/CEILING PENETRATIONS. |
| | |
| | 4)712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED |
| | BY AN APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM |
| | INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR |
| | UL 1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL |
| | OF 0.01 INCH OF WATER. THE SYSTEM SHALL HAVE AN F |
| | RATING AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT |
| | LESS THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. |
| | PLEASE INDICATE THE UL ASSEMBLY NUMBER FOR THE FLOOR |
| | PENETRATION WHERE THE PLUMBING PIPES WILL BE REMOVED |
| | AND CAPED. WHERE ANY PIPES ARE REMOVED FROM THE FLOOR |
| | CEILING/ASSEMBLY, THE HOLES SHALL BE SEALED WITH A UL |
| | ASSEMBLY WHICH SHALL MAINTAIN THE FLOOR RATING. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |