| Plan Review Notes For Permit 08040527 |
| Permit Number |
08040527 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-23 15:35:29 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1) FBC-2004 SEC. 424.2.7.1, OR FBCR-2004 SEC.R4101.7.1 | | | POOL CIRCULATING PUMPS | | | SHALL BE EQUIPPED ON THE INLET SIDE WITH | | | AN APPROVED TYPE HAIR AND LINT STRAINER | | | WHEN USED WITH A PRESSURE FILTER. | | | (DETAIL, MANUFACTURE SPEC SHEET OR ADD TO NOTES) | | | | | | 2) FBC-2004 SEC. 424.2.14.1, OR | | | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. (MANUFACTURE | | | SHEETS REQUIRED, PLEASE SUBMIT) | | | *THE MANUFACTURER'S SPEC SHEET FOR THE HEAT PUMP ARE | | | NOT INDICATING A LISTING AND AN ONLINE SEARCH BY THIS | | | PLAN REVIEWER FAILED TO FIND ONE AS WELL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|