| Plan Review Notes For Permit 08040527 |
| Permit Number |
08040527 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-21 15:23:05 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS | | | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | 1} PROVIDE A SCHEMATIC OF THE POOL WIRING AND | | | EQUIPMENT. | | | | | | 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL | | | SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO | | | BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 | | | NEC 2005.INDICATE THE RATING OF THE EXISTING SERVICE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|