2008-07-18 15:39:07DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 AMENDMENTS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW;
  
 1. PLANS SUBMITTED FOR PLAN REVIEW ONLY AT THIS TIME.
  
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 15. SHT P1.0 MISC PLUMBING FIXTURES. THE WATER
 FILTRATION SYSTEM SHALL MEET THE REQUIREMENTS OF NSF-42
 OR NSF-58 PER SECTIONS 611.1 OR 611.2. PLEASE SUBMIT
 MANUF. SPECIFICATION SHEETS SHOWING COMPLIANCE.
 ****RESPONSE NOTED, BUT MANUFACTURE SPECIFICATIONS
 SHEETS DO NOT INDICATE THAT THEY MEET THE NSF-58
 REQUIREMENTS. PER SECTION 611.2 THE FILTER MAY MEET
 WATER QUALITY ASSOCIATION STANDARD S-300 AS AN
 ALTERNATIVE BUT SHALL MEET ONE STANDARD OR THE OTHER.
 (IF THIS IS THE ONLY OUTSTANDING COMMENT PLANS CAN BE
 PROVISO'D AND PERMIT ISSUED. REQUIRED INFORMATION CAN
 BE SUBMITTED PRIOR TO FINAL PLUMBING INSPECTION).
  
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  