Plan Review Notes
Plan Review Notes For Permit 08040517
Permit Number 08040517
Review Stop M
Sequence Number 2
Notes
Date Text
2008-07-08 08:49:02REVIEW #: 2ND **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 20076 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 COMMENT #1 HAS NOT BEEN ADDRESSED.
  
 COMMENTS 2 THROUGH 5: OK
  
 ENERGY CALCULATIONS CAN NOT BE REVIEWED AT THIS TIME
 FOR THE FOLLOWING REASONS:
  
 - THE INPUT DATA REPORT IS REQUIRED TO BE ATTACHED TO
 THE COMPLIANCE FORM. SEE "IMPORTANT NOTE" ON PAGE 2 OF
 THE FORM.
  
 - COOLING LOAD CALCULATIONS OR SYSTEM SIZING SUMMARY
 SHALL BE ATTACHED TO THE ENERGY CALCULATIONS IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 - THE ENERGY CALCULATIONS SHALL BE PREPARED AND
 CERTIFIED BY A PROFESSIONAL ENGINEER OR ARCHITECT IN
 ACCORDANCE WITH FBCB 13-103.1.1.1 AND FBCB 13-103.2.
 THE PREPARER IS LISTED AS "VINOI SKARIA" AND THIS
 PERSON HAS NOT SIGNED AND SEALED THE PLANS. PAUL HUBER
 HAS SIGNED AND SEALED A COVER SHEET BUT HAS NOT SIGNED
 AND SEALED THE COMPLIANCE FORM ON THE CERTIFICATIONS
 PAGE. MR. HUBER IS NOT LISTED AS THE PREPARER OF THESE
 CALCULATIONS.
  