| Notes |
| Date |
Text |
| 2008-07-08 08:49:02 | REVIEW #: 2ND **PLAN CHECK ONLY** | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 20076 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | COMMENT #1 HAS NOT BEEN ADDRESSED. | | | | | | COMMENTS 2 THROUGH 5: OK | | | | | | ENERGY CALCULATIONS CAN NOT BE REVIEWED AT THIS TIME | | | FOR THE FOLLOWING REASONS: | | | | | | - THE INPUT DATA REPORT IS REQUIRED TO BE ATTACHED TO | | | THE COMPLIANCE FORM. SEE "IMPORTANT NOTE" ON PAGE 2 OF | | | THE FORM. | | | | | | - COOLING LOAD CALCULATIONS OR SYSTEM SIZING SUMMARY | | | SHALL BE ATTACHED TO THE ENERGY CALCULATIONS IN | | | ACCORDANCE WITH FBCB 13-407.1.ABC.1. | | | | | | - THE ENERGY CALCULATIONS SHALL BE PREPARED AND | | | CERTIFIED BY A PROFESSIONAL ENGINEER OR ARCHITECT IN | | | ACCORDANCE WITH FBCB 13-103.1.1.1 AND FBCB 13-103.2. | | | THE PREPARER IS LISTED AS "VINOI SKARIA" AND THIS | | | PERSON HAS NOT SIGNED AND SEALED THE PLANS. PAUL HUBER | | | HAS SIGNED AND SEALED A COVER SHEET BUT HAS NOT SIGNED | | | AND SEALED THE COMPLIANCE FORM ON THE CERTIFICATIONS | | | PAGE. MR. HUBER IS NOT LISTED AS THE PREPARER OF THESE | | | CALCULATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|