Plan Review Notes
Plan Review Notes For Permit 08040517
Permit Number 08040517
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-07-16 15:21:07***DENIED***
  
 PLANS ARE SUBMITTED FOR PLAN REVIEW ONLY. PLANS WILL
 REMAIN IN FAILED STATUS UNTIL ALL COMMENTS ARE
 ADDRESSED AND PLANS ARE SUBMITTED FOR PERMITTING.
  
 ALL COMMENTS FROM FIRST FIRE REVIEW HAVE BEEN ADDRESSED
 WITH THE EXCEPTION OF THE FOLLOWING:
  
 3) RESPONSE LETTER INDICATES CLASS A AND PLANS SHOW
 CLASS B. PLEASE CLARIFY IF INFORMATION DIFFERS FROM
 DRAWINGS.
  
 4) PLANS DO NOT CLEARLY SHOW ILLUMINATED EXIT SIGNS.
 SHEETS A 3.0 AND E 3.0 ILLUSTRATE EMERGENCY LIGHTING
 FACILITIES ONLY.
  
  
 NEW COMMENT:
  
 1) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED THAT
 SHALL BE MOUNTED NOT TO EXCEED 75' TRAVEL DISTANCE.
 PLEASE ADD TO PLANS OR INDICATE WHERE ON PLANS THIS
 INFORMATION IS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW