Plan Review Notes
Plan Review Notes For Permit 08040517
Permit Number 08040517
Review Stop E
Sequence Number 2
Notes
Date Text
2008-07-07 09:28:47** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THAT SOME COMMENTS ARE THE SAME AS
 PREVIOUS REVIEW. THERE ARE ALSO SOME NEW COMMENTS DUE
 TO NEW DOCUMENTS WHICH WERE NOT SUBMITTED ON PREVIOUS
 REVIEW.
  
  
 **STARBUCKS BLD OUT.
  
 1) NOTE: ** SANE NOTE **
 PLEASE KNOW PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN
 REVIEW AND HAVE NOT BEEN SUBMITTED FOR PERMIT. EVEN
 ONCE PLANS ARE FOUND TO MEET THE FLORIDA BUILDING CODE
 AND OTHER APPLICABLE LAWS REVIEW WILL STILL NOT SHOW A
 *PASSES* STATUS UNTIL PERMIT IS APPLIED. REVIEW OF
 LICENSING ETC WILL BE REQUIRED AT THAT TIME.
  
 2) NOTE: ** SAME NOTE **
 PLEASE KNOW AS THE PERMIT FOR THE BASE SHELL BUILDING
 HAS NOT YET BEEN ISSUED, ONCE PLANS ARE FOUND TO BE
 CODE COMPLIANT ETC AND PERMIT IS APPLIED, PERMIT MAY
 NOT BE ISSUED UNTIL BASE BUILDING HAS BEEN ISSUED. **
 IMPORTANT** PLEASE KEEP IN MIND IF THE BUILD OUT PERMIT
 IS ISSUED THE BASE BUILDING PLANS WILL BE REQUIRED TO
 BE UPDATED TO SHOW ALL KNOWN UNDER BUILD OUT PLANS
 BEFORE FINALS.
  
 3) NOTE: ** SAME NOTE **
 PLEASE KNOW IF THE BASE BUILDING DOES NOT RECEIVE A
 CERTIFICATE OF COMPLETION BEFORE THE BUILD OUT PERMIT
 IS ISSUED THE PLANS WILL BE REQUIRED TO CONTAIN A
 *REVIEW STAMP* SUCH AS A SHOP DRAWING REVIEW STAMP FROM
 THE BASED BUILDING DESIGNERS ON EACH PAGE FROM THE BASE
 BUILDING DESIGNER FOR THAT TRADE. THE BASE BUILDING IS
 UNDER THE RESPONSIBILITY OF THE BASE BUILDING DESIGN
 TEAM UNTIL SUCH TIME THE C OF C HAS BEEN ISSUED.
 PLEASE ALSO KNOW THAT ALL ITEMS INCORPORATED INTO THE
 BUILD OUT SUCH AS LIGHTING, LOADS, ITEMS FOR ENERGY
 CALCULATIONS ETC WILL ALL BE REQUIRED TO BE REVISED AND
 SUBMITTED ON BASE BUILDING.
  
 ** THIS INFORMATION IS GIVEN AS INFORMATION ONLY AS THE
 BUILD OUT PERMIT IS NOT YET APPLIED FOR. ONCE APPLIED,
 PLEASE MUST BE STAMPED ETC OR PERMITS WILL NOT BE
 ISSUED AS NOTED ABOVE.
  
 4) NOTE: ** SAME NOTE**
 PLEASE ALSO KNOW IF THE BUILD OUT SCOPE OF WORK IS
 APPLIED FOR UNDER A DIFFERENT CONTRACTOR THAN THE BASE
 SHELL BUILDING A LETTER OF UNDERSTANDING WILL BE
 REQUIRED BETWEEN THE TWO CONTRACTORS. THIS IS TO AVOID
 CONFLICT IN THE INSPECTIONS, BUILDING ETC.
  
  
 5) NOTE: NOTES 1-4 OF THE PREVIOUS REVIEW ARE THE SAME.
 THE RESPONSE LETTER MENTIONS THE COMMENTS WERE
 UNDERSTOOD YET NONE OF THE ITEMS PREVIOUSLY NOTED WERE
 ACTUALLY ADDRESSED. AS STATED ON PREVIOUS REVIEW, IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES REQUESTED THE
 SUBMISSION OF LIGHTING PERFORMANCE CALCULATIONS TO MEET
 FBC 13-415.2.ABC.1.1, .1.2 AND .1.3.
 THE SUBMITTED FLA-COM METHOD *C* CALCULATIONS ARE NOT
 COMPLETE. PLEASE SEE THE INPUT DATA REPORT WHICH IS
 REQUIRED TO BE PART OF THE CALCULATIONS WAS NOT
 SUBMITTED. PLEASE TAKE A LOOK AT SHEET 2 OF 7 WHICH
 SPECIFICALLY STATES THE INPUT DATA REPORT MUST BE
 INCLUDED.
 ** PLEASE SEE THE CERTIFICATION SHEET IS NOT SIGNED,
 DATED OR SEALED BY THE DESIGNER OF RECORD. IN FACT THE
 CERTIFICATION SHEET CONTAINS A PRINTED NAME OTHER THAN
 THE ENGINEER OF ARCHITECT RESPONSIBLE PER FBC 13-103.1,
 FS 471.025, FAC 61G15-23.002.
 THE SHEET WHICH WAS ATTACHED TO THE FRONT OF THE
 CALCULATIONS WHICH WAS SOME SORT OF COVER SHEET IS NOT
 ACCEPTABLE IN LIEU OF SIGNING AND SEALING SAID
 DOCUMENTS.
 ** PLEASE BE SURE ALL INFORMATION ON PLANS FOR SYSTEMS
 AND BUILDING COMPONENTS ARE PLACED INTO THE
 CALCULATIONS CORRECTLY. THE TOTAL WATTAGE AS SHOWN ON
 THE SUMMARY SHEETS OF 1204 IS NOT ACCURATE. THE
 LIGHTING ON SHEET E3.0 IS GREATER THAN SHOWN.
 PLEASE SEE OTHER COMPONENTS SUCH AS PIPING/ HOT WATER
 ETC WHICH WILL BE NOTED BY OTHER TRADES IS BLANK.
  
 7) NOTE: PLANS SHOW A NEW PANEL *C* YET PANEL IS BLANK.
 NO CIRCUITS FOR ANY SPECIFIC ELECTRICAL, NO LOAD ETC.
 PLEASE CLARIFY
 FBC 106.1.1 FOR CLARITY AND ADDITIONAL INFORMATION.
 NEC 408.4, 220, 310.16 ETC
  
  
 8) NOTE: PLEASE VERIFY LIGHTING CONTROLS AS REQUIRED
 PER 13-415.1.ABC.1.2, .1.3 AND .1.4.
 FOR EXAMPLE:
 PLEASE KNOW THE EXTERIOR LIGHTS SHALL MEET ONE OF TWO
 METHODS OF CONTROL PER 13-415.1.ABC.1.4. AT THIS TIME
 PLANS DO NOT INDICATE HOW THE DRIVE THRU LIGHTS ON
 CIRCUIT A-26 WILL MEET CODE.
 PLEASE KNOW THIS IS ONLY NOTED FOR ONE EXAMPLE AND IS
 NOT AN EXHAUSTED LIST.
 ** THIS IS THE SAME COMMENT AS PREVIOUS REVIEW. THE
 RESPONSE LETTER FROM THE DESIGNER MENTIONS TO SEE THE
 NEW FLA-COM CALCULATIONS FOR COMPLIANCE. THE FLA-COM
 CALCULATIONS DO NOT HAVE ANYTHING TO DO WITH THE
 REQUIRED METHOD OF CONTROL FOR ALL OUTSIDE/EXTERIOR
 LIGHTING. ONCE AGAIN PLEASE SEE THE SECTION OF THE CODE
 ABOVE WITH RESPECT TO CONTROLS.
 THE DETAILS #9 AND #10 ON SHEET E4.0 STILL DOES NOT
 SHOW CIRCUIT A-26 AND ALSO DOES NOT INDICATE THE
 REQUIRED BACK UP FOR ANY ASTRONOMICAL TIME CLOCK.
  
 9) NOTE: PLEASE BE SURE PLANS COORDINATE WITH THE BASE
 BUILDING PLANS FOR DESIGN ETC
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]