| 2008-07-07 09:28:47 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE THAT SOME COMMENTS ARE THE SAME AS |
| | PREVIOUS REVIEW. THERE ARE ALSO SOME NEW COMMENTS DUE |
| | TO NEW DOCUMENTS WHICH WERE NOT SUBMITTED ON PREVIOUS |
| | REVIEW. |
| | |
| | |
| | **STARBUCKS BLD OUT. |
| | |
| | 1) NOTE: ** SANE NOTE ** |
| | PLEASE KNOW PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN |
| | REVIEW AND HAVE NOT BEEN SUBMITTED FOR PERMIT. EVEN |
| | ONCE PLANS ARE FOUND TO MEET THE FLORIDA BUILDING CODE |
| | AND OTHER APPLICABLE LAWS REVIEW WILL STILL NOT SHOW A |
| | *PASSES* STATUS UNTIL PERMIT IS APPLIED. REVIEW OF |
| | LICENSING ETC WILL BE REQUIRED AT THAT TIME. |
| | |
| | 2) NOTE: ** SAME NOTE ** |
| | PLEASE KNOW AS THE PERMIT FOR THE BASE SHELL BUILDING |
| | HAS NOT YET BEEN ISSUED, ONCE PLANS ARE FOUND TO BE |
| | CODE COMPLIANT ETC AND PERMIT IS APPLIED, PERMIT MAY |
| | NOT BE ISSUED UNTIL BASE BUILDING HAS BEEN ISSUED. ** |
| | IMPORTANT** PLEASE KEEP IN MIND IF THE BUILD OUT PERMIT |
| | IS ISSUED THE BASE BUILDING PLANS WILL BE REQUIRED TO |
| | BE UPDATED TO SHOW ALL KNOWN UNDER BUILD OUT PLANS |
| | BEFORE FINALS. |
| | |
| | 3) NOTE: ** SAME NOTE ** |
| | PLEASE KNOW IF THE BASE BUILDING DOES NOT RECEIVE A |
| | CERTIFICATE OF COMPLETION BEFORE THE BUILD OUT PERMIT |
| | IS ISSUED THE PLANS WILL BE REQUIRED TO CONTAIN A |
| | *REVIEW STAMP* SUCH AS A SHOP DRAWING REVIEW STAMP FROM |
| | THE BASED BUILDING DESIGNERS ON EACH PAGE FROM THE BASE |
| | BUILDING DESIGNER FOR THAT TRADE. THE BASE BUILDING IS |
| | UNDER THE RESPONSIBILITY OF THE BASE BUILDING DESIGN |
| | TEAM UNTIL SUCH TIME THE C OF C HAS BEEN ISSUED. |
| | PLEASE ALSO KNOW THAT ALL ITEMS INCORPORATED INTO THE |
| | BUILD OUT SUCH AS LIGHTING, LOADS, ITEMS FOR ENERGY |
| | CALCULATIONS ETC WILL ALL BE REQUIRED TO BE REVISED AND |
| | SUBMITTED ON BASE BUILDING. |
| | |
| | ** THIS INFORMATION IS GIVEN AS INFORMATION ONLY AS THE |
| | BUILD OUT PERMIT IS NOT YET APPLIED FOR. ONCE APPLIED, |
| | PLEASE MUST BE STAMPED ETC OR PERMITS WILL NOT BE |
| | ISSUED AS NOTED ABOVE. |
| | |
| | 4) NOTE: ** SAME NOTE** |
| | PLEASE ALSO KNOW IF THE BUILD OUT SCOPE OF WORK IS |
| | APPLIED FOR UNDER A DIFFERENT CONTRACTOR THAN THE BASE |
| | SHELL BUILDING A LETTER OF UNDERSTANDING WILL BE |
| | REQUIRED BETWEEN THE TWO CONTRACTORS. THIS IS TO AVOID |
| | CONFLICT IN THE INSPECTIONS, BUILDING ETC. |
| | |
| | |
| | 5) NOTE: NOTES 1-4 OF THE PREVIOUS REVIEW ARE THE SAME. |
| | THE RESPONSE LETTER MENTIONS THE COMMENTS WERE |
| | UNDERSTOOD YET NONE OF THE ITEMS PREVIOUSLY NOTED WERE |
| | ACTUALLY ADDRESSED. AS STATED ON PREVIOUS REVIEW, IF |
| | THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES REQUESTED THE |
| | SUBMISSION OF LIGHTING PERFORMANCE CALCULATIONS TO MEET |
| | FBC 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | THE SUBMITTED FLA-COM METHOD *C* CALCULATIONS ARE NOT |
| | COMPLETE. PLEASE SEE THE INPUT DATA REPORT WHICH IS |
| | REQUIRED TO BE PART OF THE CALCULATIONS WAS NOT |
| | SUBMITTED. PLEASE TAKE A LOOK AT SHEET 2 OF 7 WHICH |
| | SPECIFICALLY STATES THE INPUT DATA REPORT MUST BE |
| | INCLUDED. |
| | ** PLEASE SEE THE CERTIFICATION SHEET IS NOT SIGNED, |
| | DATED OR SEALED BY THE DESIGNER OF RECORD. IN FACT THE |
| | CERTIFICATION SHEET CONTAINS A PRINTED NAME OTHER THAN |
| | THE ENGINEER OF ARCHITECT RESPONSIBLE PER FBC 13-103.1, |
| | FS 471.025, FAC 61G15-23.002. |
| | THE SHEET WHICH WAS ATTACHED TO THE FRONT OF THE |
| | CALCULATIONS WHICH WAS SOME SORT OF COVER SHEET IS NOT |
| | ACCEPTABLE IN LIEU OF SIGNING AND SEALING SAID |
| | DOCUMENTS. |
| | ** PLEASE BE SURE ALL INFORMATION ON PLANS FOR SYSTEMS |
| | AND BUILDING COMPONENTS ARE PLACED INTO THE |
| | CALCULATIONS CORRECTLY. THE TOTAL WATTAGE AS SHOWN ON |
| | THE SUMMARY SHEETS OF 1204 IS NOT ACCURATE. THE |
| | LIGHTING ON SHEET E3.0 IS GREATER THAN SHOWN. |
| | PLEASE SEE OTHER COMPONENTS SUCH AS PIPING/ HOT WATER |
| | ETC WHICH WILL BE NOTED BY OTHER TRADES IS BLANK. |
| | |
| | 7) NOTE: PLANS SHOW A NEW PANEL *C* YET PANEL IS BLANK. |
| | NO CIRCUITS FOR ANY SPECIFIC ELECTRICAL, NO LOAD ETC. |
| | PLEASE CLARIFY |
| | FBC 106.1.1 FOR CLARITY AND ADDITIONAL INFORMATION. |
| | NEC 408.4, 220, 310.16 ETC |
| | |
| | |
| | 8) NOTE: PLEASE VERIFY LIGHTING CONTROLS AS REQUIRED |
| | PER 13-415.1.ABC.1.2, .1.3 AND .1.4. |
| | FOR EXAMPLE: |
| | PLEASE KNOW THE EXTERIOR LIGHTS SHALL MEET ONE OF TWO |
| | METHODS OF CONTROL PER 13-415.1.ABC.1.4. AT THIS TIME |
| | PLANS DO NOT INDICATE HOW THE DRIVE THRU LIGHTS ON |
| | CIRCUIT A-26 WILL MEET CODE. |
| | PLEASE KNOW THIS IS ONLY NOTED FOR ONE EXAMPLE AND IS |
| | NOT AN EXHAUSTED LIST. |
| | ** THIS IS THE SAME COMMENT AS PREVIOUS REVIEW. THE |
| | RESPONSE LETTER FROM THE DESIGNER MENTIONS TO SEE THE |
| | NEW FLA-COM CALCULATIONS FOR COMPLIANCE. THE FLA-COM |
| | CALCULATIONS DO NOT HAVE ANYTHING TO DO WITH THE |
| | REQUIRED METHOD OF CONTROL FOR ALL OUTSIDE/EXTERIOR |
| | LIGHTING. ONCE AGAIN PLEASE SEE THE SECTION OF THE CODE |
| | ABOVE WITH RESPECT TO CONTROLS. |
| | THE DETAILS #9 AND #10 ON SHEET E4.0 STILL DOES NOT |
| | SHOW CIRCUIT A-26 AND ALSO DOES NOT INDICATE THE |
| | REQUIRED BACK UP FOR ANY ASTRONOMICAL TIME CLOCK. |
| | |
| | 9) NOTE: PLEASE BE SURE PLANS COORDINATE WITH THE BASE |
| | BUILDING PLANS FOR DESIGN ETC |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |