| 2008-04-29 12:55:37 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING W/2007 AMENDMENTS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. PLANS SUBMITTED FOR PLAN REVIEW ONLY AT THIS TIME. |
| | |
| | 2. ALL SHEETS. THE SIGNATURES ON THE SEAL ARE NOT |
| | ORIGINAL "WET" SEALS, BUT STAMPED OR PHOTO COPIED. |
| | ORIGINAL SIGNATURES ARE REQUIRED PER FAC 61G15-002(2), |
| | 61G1-16.004(5) & FS 471.025, 481.221. |
| | |
| | 3. SHT A6.0 DETAIL #5 INDICATES THE BOTTOM OF MIRROR AT |
| | 1'8" ABOVE THE FLOOR. WITH THE CLEARANCES OF THE LAV |
| | REQUIRED TO BE 29" AND THE RIM OF THE LAV TO BE A |
| | MINIMUM OF 34" PLEASE EXPLAIN HOW THE MIRROR CAN BE |
| | THAT LOW. SECTION 11-4.19.2. PER SECTION 11-4.19.6 THE |
| | BOTTOM OF THE MIRROR SHALL BE MAX 40". PLEASE CLARIFY. |
| | |
| | 4. SHT A6.0 DETAIL #5 THE GRAB BARS AT THE WATER CLOSET |
| | ARE SHOWN AT 1'4". THE GRAB BARS SHALL BE 33" - 36" PER |
| | SECTION 11-4.16..4 & FIG. 11-28. |
| | |
| | 5. SHT A6.0 DETAIL #5 THE LAV IS INDICATED AS 9" OFF |
| | THE WALL TO THE CENTERLINE OF THE FIXTURE. THE LAV |
| | SHALL BE MINIMUM 15" OFF THE WALL TO BE CENTERED ON THE |
| | 30" DIMENSION OF THE CLEAR FLOOR SPACE REQUIRED BY |
| | SECTION 11-4.19.3. |
| | |
| | 6. SHT A6.0 DETAIL #9 INDICATES THE W/C TO BE 9" OFF |
| | THE WALL TO THE CENTERLINE OF THE FIXTURE. THE W/C |
| | SHALL BE 1'6" OFF THE WALL TO THE C/L PER FIG. 11-28. |
| | |
| | 7. SHT A6.0 DETAIL #9 THE GRAB BARS FOR THE W/C IS |
| | INDICATED TO BE 1'4" ABOVE THE FLOOR. THE GRAB BARS |
| | SHALL BE 33" - 36" PER SECTION 11-4.16..4 & FIG. |
| | 11-28. |
| | |
| | 8. SHT A6.0 DETAIL #9 THE W/C HEIGHT IS INDICATED AS |
| | 9". THE HEIGHT SHALL BE INDICATED AS BETWEEN 17" & 19" |
| | PER SECTION 11-4.16.3. |
| | |
| | 9. SHT A6.0 DETAIL #10 HEIGHT OF THE LAV IS INDICATED |
| | AS 1'5". THE CLEARANCE REQUIRED IS 29". SECTION |
| | 11-4.19.2. PLEASE CLARIFY. |
| | |
| | 10. SHT A6.0 DETAIL #16 THE GRAB BARS FOR THE W/C IS |
| | INDICATED TO BE 1'4" ABOVE THE FLOOR. THE GRAB BARS |
| | SHALL BE 33" - 36" PER SECTION 11-4.16..4 & FIG. |
| | 11-28. |
| | |
| | 11. SHT A6.0 DETAIL #17 INDICATES THE W/C TO BE 9" OFF |
| | THE WALL TO THE CENTERLINE OF THE FIXTURE. THE W/C |
| | SHALL BE 1'6" OFF THE WALL TO THE C/L PER FIG. 11-28. |
| | |
| | 12. SHT A6.0 DETAIL #17 INDICATES THE BOTTOM OF MIRROR |
| | AT 1'8" ABOVE THE FLOOR. WITH THE CLEARANCES OF THE LAV |
| | REQUIRED TO BE 29" AND THE RIM OF THE LAV TO BE A |
| | MINIMUM OF 34" PLEASE EXPLAIN HOW THE MIRROR CAN BE |
| | THAT LOW. SECTION 11-4.19.2. PER SECTION 11-4.19.6 THE |
| | BOTTOM OF THE MIRROR SHALL BE MAX 40". PLEASE CLARIFY. |
| | |
| | 13. SHT A6.0 DETAIL #17 THE GRAB BARS FOR THE W/C IS |
| | INDICATED TO BE 1'4" ABOVE THE FLOOR. THE GRAB BARS |
| | SHALL BE 33" - 36" PER SECTION 11-4.16..4 & FIG. |
| | 11-28. |
| | |
| | 14. SHT A6.0 DETAIL #18 THE LAV IS INDICATED AS 1'5" TO |
| | THE RIM. THE CLEARANCE REQUIRED IS 29". SECTION |
| | 11-4.19.2. PLEASE CLARIFY. |
| | |
| | 15. SHT P1.0 MISC PLUMBING FIXTURES. THE WATER |
| | FILTRATION SYSTEM SHALL MEET THE REQUIREMENTS OF NSF-42 |
| | OR NSF-58 PER SECTIONS 611.1 OR 611.2. PLEASE SUBMIT |
| | MANUF. SPECIFICATION SHEETS SHOWING COMPLIANCE. |
| | |
| | 16. SHT P1.0 BUILDING CODE NOTES SHALL INCLUDE 2007 |
| | AMENDMENTS. ALSO THE CODE NOTES SHALL STATE CITY OF |
| | WEST PALM BEACH, NOT CITY OF CAPE CORAL. SECTION |
| | 106.3.5. |
| | |
| | 17. SHT P2.0 SUPPLY PIPING DIAGRAM SHALL BE SUBMITTED |
| | IN AN ISOMETRIC FORM TO REFLECT THE FLOOR PLAN AMD |
| | ACTUAL PIPING INSTALLATION. SECTIONS 106.1.3 & |
| | 106.3.5.1.3. SHOW THE WATER HAMMER ARRESTORS REQUIRED |
| | BY SECTION 604.9 AT THE DISH WASHER AND AT THE ICE |
| | MAKER. WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING. |
| | PDI-WH 201. |
| | |
| | 18. SHT P2.0 PLUMBING SCHEDULE. ITEMS P017, P026, P036, |
| | P068 & P080 SHOW NO WATER SUPPLY. PLEASE CLARIFY. |
| | SECTION 601.1 & TABLE 604.5. |
| | |
| | 19. SHT P2.0 PLUMBING SCHEDULE. INTEM P358 OUTDOOR |
| | SPIGOT INDICATES 3/8" INLET. TABLE 604.5 INDICATES |
| | MINIMUM SIZE WATER SUPPLY IS 1/2". ALSO 3/4" SUPPLY |
| | LINE IS SHOWN TO THE SPIGOT/HOSE BIBB. PLEASE CLARIFY. |
| | |
| | |
| | 20. SHT P2.0 PLUMBING SCHEDULE. ITEM P360 FAUCET SHOWS |
| | NO WATER SUPPLY. PLEASE CLARIFY. SECTIONS 106.1.1 & |
| | 106.1. |
| | |
| | 21. SHT P2.0 PLUMBING SCHEDULE. ITEM P035 INDICATES 3 |
| | FLOOR DRAINS AND REFERS TO SHT P3.0 WHICH ONLY |
| | INDICATES 2 FLOOR DRAINS ON THE FLOOR PLAN AND PLUMBING |
| | SCHEDULE. PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1. |
| | |
| | 22. SHT P2.0 PLUMBING SCHEDULE. ITEM P367 INDICATES QTY |
| | 1 BUT 2 ARE SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | |
| | 23. SHT P2.0 NOTE #20 INDICATES A WATER SUB METER. THE |
| | SUB METER WAS NOT FOUND ON THE FLOOR PLAN. PLEASE |
| | CORRELATE/CLARIFY. SECTION 106.1.1. |
| | |
| | 24. SHT P2.0 NOTES #21, #29 & #31 WERE NOT FOUND ON THE |
| | FLOOR PLAN. PLEASE CORRELATE/CLARIFY. SECTION 106.1.1. |
| | |
| | 25. SHT P3.0 SUBMIT THE SANITARY RISER DIAGRAM IN |
| | ISOMETRIC FORM THAT REFLECT THE FLOOR PLAN AND ACTUAL |
| | PIPING INSTALLATION. SECTIONS 106.1.3 & 106.3.5.1.3. |
| | |
| | 26. SHT P3.0 THE DISHWASHER SHALL CONNECT TO THE |
| | SANITARY SYSTEM, NOT THE GREASE SYSTEM PER ATRICLE III |
| | SECTION 90-124(7)(B). PLEASE SHOW ON FLOOR P[LAN AND |
| | ISOMETRIC RISER DIAGRAM. |
| | |
| | 27. SHT P3.0 NOTE #4 INDICATES INDIRECT WASTE RECEPTOR, |
| | BUT THE PLUMBING SCHEDULE INDICATES 2" DIRECT WASTE |
| | CONNECTION. PLEASE CORRELATE/CLARIFY. PER SECTIONS |
| | 802.1 & 802.1.1 UNLESS THERE IS FOOD HANDLING/STORAGE |
| | IN THE 3 COMPARTMENT SINK, A DIRECT CONNECTION IS |
| | APPROVED. |
| | |
| | 28. SHT P3.0 NOTE #15 CONDENSATE SHALL DRAIN OUT OF THE |
| | BUILDING SEPARATELY AND CONNECT TO A DRYWELL, CATCH |
| | BASIN, STORM LINE OR DRAIN TO A PLANTED AREA. IF |
| | CONNECTING TO A STORM LINE, A RELIEF VENT, (GOOSENECK), |
| | IS REQUIRED AS THE CONDENSATE EXITS THE BUILDING. |
| | ARTICLE III SECTION 90-125(5). |
| | |
| | 29. SHT P4.0 DETAIL #7 INDICATES 1" MINIMUM AIR GAP. 3" |
| | AIR GAP REQUIRED PER SECTION 802.2.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |