| 2008-05-12 09:34:10 | REVIEW #: 1ST. ***PLAN CHECK ONLY** |
| | ACTION: |
| | |
| | FBC 2004 CODE FAMILY W/ 2005, 2006 AND 2007 SUPPLEMENTS |
| | |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. THIS APPEARS TO BE A TENANT BUILD-OUT IN A SHELL |
| | BUILDING. A PERMIT FOR THE SHELL BUILDING HAS NOT BEEN |
| | ISSUED. THIS PERMIT MAY NOT BE ISSUED PRIOR TO THE |
| | SHELL BUILDING. IF THIS PERMIT IS APPLIED FOR PRIOR TO |
| | COMPLETION OF THE SHELL BUILDING, A LETTER FROM THE |
| | BASE BUILDING CONTRACTOR ALLOWING THE TENANT CONTRACTOR |
| | TO START WORK PRIOR TO A CERTIFICATE OF COMPLETION WILL |
| | BE REQUIRED. A JOINT LETTER FROM THE DEVELOPER AND BOTH |
| | CONTRACTORS WILL ALSO BE REQUIRED ACKNOWLEDGING THAT |
| | ANY DISPUTE OVER RESPONSIBILITY DOES NOT RELIEVE ANY |
| | PARTY FROM DEMONSTRATING CODE COMPLIANCE PRIOR TO |
| | CERTIFICATE OF OCCUPANCY. |
| | |
| | 2. SIGNED AND SEALED PLANS SHALL CONTAIN THE ORIGINAL |
| | SIGNATURE OF THE DESIGN PROFESSIONAL. A TITLE BLOCK |
| | CONFORMING TO FAC RULE 61G15-23.002 IS REQUIRED ON EACH |
| | SET OF PLANS. IF THE DESIGNER OF RECORD IS PRACTICING |
| | AS AN INDIVIDUAL, REMOVE THE BUSINESS NAME FROM THE |
| | ENGINEER?S TITLE BLOCK. |
| | |
| | 3. PG M2.0: HVAC FLOOR PLAN, MUCH OF THE DUCTWORK IS |
| | NOT VISIBLE ON PLANS BECAUSE IT BLENDS IN WITH THE |
| | CEILING GRID. PLEASE SHOW CLEARLY THE LOCATION AND SIZE |
| | OF ALL DUCTWORK IN ORDER TO FACILITATE A COMPLETE |
| | REVIEW. DUCTWORK CAN NOT BE REVIEWED AT THIS TIME. FBCM |
| | 603.1, FBCB 106.1.1. |
| | |
| | 4. PG M2.0: VENTILATION CALCULATIONS SHALL BE BASED ON |
| | THE 2004 FBCM, NOT THE 2007. THE 2007 FBC WILL NOT BE |
| | ADOPTED OR ENFORCED PRIOR TO 10/1/2008. THE CURRENT |
| | MECHANICAL CODE IN EFFECT AT THIS TIME IS THE 2004 FBCM |
| | WITH 2006 AMENDMENTS. |
| | |
| | 5. PG M2.0: NO INFORMATION COULD BE FOUND ON PLANS |
| | REGARDING AMOUNT OF EXHAUST BEING PROVIDED FOR |
| | RESTROOMS. PROVIDE VENTILATION RATE INFORMATION IN |
| | ACCORDANCE WITH FBCM TABLE 403.3. ALSO PROVIDE AIR |
| | BALANCE DATA SHOWING COMPLIANCE WITH FBCB |
| | 13-409.1.ABC.2. |
| | |