| Plan Review Notes For Permit 08040517 |
| Permit Number |
08040517 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-21 11:27:02 | ***DENIED*** | | | | | | 1) THE ADDRESS ON THE BUILDING IS REQUIRED TO BE A | | | MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND CONTRASTING | | | WITH THE BACKGROUND. ADDRESS SHALL COMPLY WITH CITY OF | | | WEST PALM BEACH REQUIREMENTS FOR COMMERCIAL BUILDINGS. | | | SHT A-1.0, NOTE 2 | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALSS AND CEILING IN TERMS OF CLASS A, B, OR C. | | | | | | 4) AN EXIT SIGN IS SHOWN AT THE VESTIBULE. PLEASE | | | EXPLAIN EXITING ARRANGEMENTS AT THAT LOCATION AS IT | | | DOES NOT APPEAR CLEAR AND OBVIOUS. | | | | | | 5) DOORS SHALL COMPLY WITH NFPA 101, SECTION 7.2.1. | | | | | | 6) AT THIS TIME, A PERMIT HAS NOT BEEN ISSUED FOR THE | | | SHELL BUILDING WHICH IMPACTS THIS REVIEW. PLEASE SEE | | | OTHER REVIEW COMMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|