Plan Review Notes
Plan Review Notes For Permit 08040517
Permit Number 08040517
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-05-21 11:27:02***DENIED***
  
 1) THE ADDRESS ON THE BUILDING IS REQUIRED TO BE A
 MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND CONTRASTING
 WITH THE BACKGROUND. ADDRESS SHALL COMPLY WITH CITY OF
 WEST PALM BEACH REQUIREMENTS FOR COMMERCIAL BUILDINGS.
 SHT A-1.0, NOTE 2
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALSS AND CEILING IN TERMS OF CLASS A, B, OR C.
  
 4) AN EXIT SIGN IS SHOWN AT THE VESTIBULE. PLEASE
 EXPLAIN EXITING ARRANGEMENTS AT THAT LOCATION AS IT
 DOES NOT APPEAR CLEAR AND OBVIOUS.
  
 5) DOORS SHALL COMPLY WITH NFPA 101, SECTION 7.2.1.
  
 6) AT THIS TIME, A PERMIT HAS NOT BEEN ISSUED FOR THE
 SHELL BUILDING WHICH IMPACTS THIS REVIEW. PLEASE SEE
 OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756