Plan Review Notes
Plan Review Notes For Permit 08040517
Permit Number 08040517
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-28 15:04:40** DENIED **
  
 **STARBUCKS BLD OUT.
  
 1) NOTE: PLEASE KNOW PLANS HAVE ONLY BEEN SUBMITTED FOR
 PLAN REVIEW AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
 EVEN ONCE PLANS ARE FOUND TO MEET THE FLORIDA BUILDING
 CODE AND OTHER APPLICABLE LAWS REVIEW WILL STILL NOT
 SHOW A *PASSES* STATUS UNTIL PERMIT IS APPLIED. REVIEW
 OF LICENSING ETC WILL BE REQUIRED AT THAT TIME.
  
 2) NOTE: PLEASE KNOW AS THE PERMIT FOR THE BASE SHELL
 BUILDING HAS NOT YET BEEN ISSUED, ONCE PLANS ARE FOUND
 TO BE CODE COMPLIANT ETC AND PERMIT IS APPLIED, PERMIT
 MAY NOT BE ISSUED UNTIL BASE BUILDING HAS BEEN ISSUED.
 ** IMPORTANT** PLEASE KEEP IN MIND IF THE BUILD OUT
 PERMIT IS ISSUED THE BASE BUILDING PLANS WILL BE
 REQUIRED TO BE UPDATED TO SHOW ALL KNOWN UNDER BUILD
 OUT PLANS BEFORE FINALS.
  
 3) NOTE: PLEASE KNOW IF THE BASE BUILDING DOES NOT
 RECEIVE A CERTIFICATE OF COMPLETION BEFORE THE BUILD
 OUT PERMIT IS ISSUED THE PLANS WILL BE REQUIRED TO
 CONTAIN A *REVIEW STAMP* SUCH AS A SHOP DRAWING REVIEW
 STAMP FROM THE BASED BUILDING DESIGNERS ON EACH PAGE
 FROM THE BASE BUILDING DESIGNER FOR THAT TRADE. THE
 BASE BUILDING IS UNDER THE RESPONSIBILITY OF THE BASE
 BUILDING DESIGN TEAM UNTIL SUCH TIME THE C OF C HAS
 BEEN ISSUED.
 PLEASE ALSO KNOW THAT ALL ITEMS INCORPORATED INTO THE
 BUILD OUT SUCH AS LIGHTING, LOADS, ITEMS FOR ENERGY
 CALCULATIONS ETC WILL ALL BE REQUIRED TO BE REVISED AND
 SUBMITTED ON BASE BUILDING.
  
 ** THIS INFORMATION IS GIVEN AS INFORMATION ONLY AS THE
 BUILD OUT PERMIT IS NOT YET APPLIED FOR. ONCE APPLIED,
 PLEASE MUST BE STAMPED ETC OR PERMITS WILL NOT BE
 ISSUED AS NOTED ABOVE.
  
 4) NOTE: PLEASE ALSO KNOW IF THE BUILD OUT SCOPE OF
 WORK IS APPLIED FOR UNDER A DIFFERENT CONTRACTOR THAN
 THE BASE SHELL BUILDING A LETTER OF UNDERSTANDING WILL
 BE REQUIRED BETWEEN THE TWO CONTRACTORS. THIS IS TO
 AVOID CONFLICTS IN THE INSPECTIONS, BUILDING ETC.
  
 5) NOTE: PLEASE SEE THAT BOTH SETS OF PLANS ARE NOT
 SIGNED WITH ORIGINAL SIGNATURES FROM ANY DESIGNER. IN
 FACT BOTH THE ARCHITECTURAL AND MEP PLANS CONTAIN
 RAISED SEALS OVER DIGITAL SIGNATURES. THIS IS NOT
 PERMITTED UNDER FS 471.025, 481.221. THESE SHALLNOT
 BE *RUBBERSTAMPS*, *PHOTO-COPIES* ETCPLEASE ALSO SEE
 FLORIDA ADMINISTRATIVE CODES 61G15-23.002,
 61G1-16.004.
 PLEASE KNOW ONE COMPLETE SET OF PLANS WILL BE RETAINED
 AT THIS TIME. PLANS ARE REQUIRED TO CONTAIN ORIGINAL
 DATE, SIGNATURE AND RAISED SEAL. THIS NOTE IS FOR ALL
 TRADES AND ALL REVIEWS WHETHER OR NOT COMMENT IS MADE
 BY OTHER TRADE REVIEWER(S).
  
 6) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS. FOR EXAMPLE, THE SHEET G1.0 STATES THE 1999
 NATIONAL ELECTRICAL CODE. PLEASE KNOW THERE HAVE BEEN
 TWO CODE CHANGES SINCE THIS 1999 NFPA-70 HAS BEEN IN
 EFFECT. THE 1999 EDITION IN THE STATE OF FLORIDA WAS NO
 LONGER IN EFFECT AFTER JULY 2003. PLEASE SEE THE LIST
 BELOW.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 ** THESE ARE TO BE STATED ON ELECTRICAL PLANS AS WELL
 AS COVER SHEET. THE 2003 LS CODE IS ALREADY STATED ON
 G1.0.
  
 7) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR THE FIRM CASCO PER FLORIDA STATUTES 481.0219 AND
 471.023. MISSING REQUIRED CERTIFICATE OF AUTHORIZATION
 NUMBER FOR BOTH THE ARCHITECTURAL BUSINESS AND
 ENGINEERING BUSINESS.
 THIS IS REQUIRED FOR BOTH SERVICES BEING OFFERED.
 PLEASE ALSO KNOW THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADE WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE REVIEWER(S).
  
 8) NOTE: PLEASE VERIFY LOADS AS THE PLANS ON E2.1 SHOWS
 A LOAD TOTAL OF 316.9 AMPS ON A PANEL *A* WHICH IS ONLY
 RATED 200AMPS.
 PLEASE VERIFY THE SERVICE AS NOTED ABOVE THESE PLANS
 SHOWS A 200AMP SERVICE ON SHEET E2.1 AND SHEET E4.0
 SHOWS AND MENTIONS 400AMP SERVICE. AS THESE DO NOT
 COORDINATE AND THE 200AMP SERVICE AS SHOWN ON E2.1 IS
 NOT SUFFICIENT THESE ITEMS WILL BE REQUIRED TO BE
 ADJUSTED TO MEET MINIMUM CODE COMPLIANCE.
 PLEASE ALSO SUBMIT LOAD CALCULATIONS ON PANEL *B* AS
 THE LOADS IS SHOWN AS 100AMPS ON A 100AMPS BREAKER.
 PLEASE PROVIDE MORE INFORMATION ON LOAD CALCULATIONS
 FOR AL EQUIPMENT. PLEASE VERIFY AND SHOW HEAT LOADS ON
 RT UNITS.
 PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT PROTECTION
 FOR HEAT STRIPS W/ RT UNITS.
 PLEASE SEE NEC 220, 215.3, 215.5, 310.16, 240.4 ETC FBC
 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 9) NOTE: PLEASE SEE NO LIGHTING PERFORMANCE
 CALCULATIONS WERE SUBMITTED AS REQUIRED PER 13-415.2,
 13-415.2.ABC.1.1, .1.2. PLEASE KNOW ANY CHANGES TO
 EXTERIOR LIGHTING SHALL MEET 13-415.2.ABC.1.3. PLEASE
 SUBMIT LP CALCULATIONS. AS NONE WERE SUBMITTED AT THIS
 TIME MINIMUM CODE COMPLIANCE REVIEW FOR THESE CAN NOT
 BE DONE. ** THIS OFFICE CAN NOT EMPHASIZE ENOUGH PLEASE
 BE SURE TO SEE THE CODE SECTIONS AS NOTED ABOVEAND
 PLEASE BE SURE ALL LIGHTING ON PLANS ARE INCLUDED WITH
 THE CALCULATIONS.
  
 10) NOTE: PLEASE VERIFY LIGHTING CONTROLS AS REQUIRED
 PER 13-415.1.ABC.1.2, .1.3 AND .1.4.
 FOR EXAMPLE:
 PLEASE KNOW THE EXTERIOR LIGHTS SHALL MEET ONE OF TWO
 METHODS OF CONTROL PER 13-415.1.ABC.1.4. AT THIS TIME
 PLANS DO NOT INDICATE HOW THE DRIVE THRU LIGHTS ON
 CIRCUIT A-26 WILL MEET CODE.
 PLEASE KNOW THIS IS ONLY NOTED FOR ONE EXAMPLE AND IS
 NOT AN EXHAUSTED LIST.
  
 11) NOTE: PLEASE SEE NO TRACK LIGHTING LOADS SHWON PER
 220.43B.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]