| Date |
Text |
| 2008-04-28 15:04:40 | ** DENIED ** |
| | |
| | **STARBUCKS BLD OUT. |
| | |
| | 1) NOTE: PLEASE KNOW PLANS HAVE ONLY BEEN SUBMITTED FOR |
| | PLAN REVIEW AND HAVE NOT BEEN SUBMITTED FOR PERMIT. |
| | EVEN ONCE PLANS ARE FOUND TO MEET THE FLORIDA BUILDING |
| | CODE AND OTHER APPLICABLE LAWS REVIEW WILL STILL NOT |
| | SHOW A *PASSES* STATUS UNTIL PERMIT IS APPLIED. REVIEW |
| | OF LICENSING ETC WILL BE REQUIRED AT THAT TIME. |
| | |
| | 2) NOTE: PLEASE KNOW AS THE PERMIT FOR THE BASE SHELL |
| | BUILDING HAS NOT YET BEEN ISSUED, ONCE PLANS ARE FOUND |
| | TO BE CODE COMPLIANT ETC AND PERMIT IS APPLIED, PERMIT |
| | MAY NOT BE ISSUED UNTIL BASE BUILDING HAS BEEN ISSUED. |
| | ** IMPORTANT** PLEASE KEEP IN MIND IF THE BUILD OUT |
| | PERMIT IS ISSUED THE BASE BUILDING PLANS WILL BE |
| | REQUIRED TO BE UPDATED TO SHOW ALL KNOWN UNDER BUILD |
| | OUT PLANS BEFORE FINALS. |
| | |
| | 3) NOTE: PLEASE KNOW IF THE BASE BUILDING DOES NOT |
| | RECEIVE A CERTIFICATE OF COMPLETION BEFORE THE BUILD |
| | OUT PERMIT IS ISSUED THE PLANS WILL BE REQUIRED TO |
| | CONTAIN A *REVIEW STAMP* SUCH AS A SHOP DRAWING REVIEW |
| | STAMP FROM THE BASED BUILDING DESIGNERS ON EACH PAGE |
| | FROM THE BASE BUILDING DESIGNER FOR THAT TRADE. THE |
| | BASE BUILDING IS UNDER THE RESPONSIBILITY OF THE BASE |
| | BUILDING DESIGN TEAM UNTIL SUCH TIME THE C OF C HAS |
| | BEEN ISSUED. |
| | PLEASE ALSO KNOW THAT ALL ITEMS INCORPORATED INTO THE |
| | BUILD OUT SUCH AS LIGHTING, LOADS, ITEMS FOR ENERGY |
| | CALCULATIONS ETC WILL ALL BE REQUIRED TO BE REVISED AND |
| | SUBMITTED ON BASE BUILDING. |
| | |
| | ** THIS INFORMATION IS GIVEN AS INFORMATION ONLY AS THE |
| | BUILD OUT PERMIT IS NOT YET APPLIED FOR. ONCE APPLIED, |
| | PLEASE MUST BE STAMPED ETC OR PERMITS WILL NOT BE |
| | ISSUED AS NOTED ABOVE. |
| | |
| | 4) NOTE: PLEASE ALSO KNOW IF THE BUILD OUT SCOPE OF |
| | WORK IS APPLIED FOR UNDER A DIFFERENT CONTRACTOR THAN |
| | THE BASE SHELL BUILDING A LETTER OF UNDERSTANDING WILL |
| | BE REQUIRED BETWEEN THE TWO CONTRACTORS. THIS IS TO |
| | AVOID CONFLICTS IN THE INSPECTIONS, BUILDING ETC. |
| | |
| | 5) NOTE: PLEASE SEE THAT BOTH SETS OF PLANS ARE NOT |
| | SIGNED WITH ORIGINAL SIGNATURES FROM ANY DESIGNER. IN |
| | FACT BOTH THE ARCHITECTURAL AND MEP PLANS CONTAIN |
| | RAISED SEALS OVER DIGITAL SIGNATURES. THIS IS NOT |
| | PERMITTED UNDER FS 471.025, 481.221. THESE SHALLNOT |
| | BE *RUBBERSTAMPS*, *PHOTO-COPIES* ETCPLEASE ALSO SEE |
| | FLORIDA ADMINISTRATIVE CODES 61G15-23.002, |
| | 61G1-16.004. |
| | PLEASE KNOW ONE COMPLETE SET OF PLANS WILL BE RETAINED |
| | AT THIS TIME. PLANS ARE REQUIRED TO CONTAIN ORIGINAL |
| | DATE, SIGNATURE AND RAISED SEAL. THIS NOTE IS FOR ALL |
| | TRADES AND ALL REVIEWS WHETHER OR NOT COMMENT IS MADE |
| | BY OTHER TRADE REVIEWER(S). |
| | |
| | 6) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS. FOR EXAMPLE, THE SHEET G1.0 STATES THE 1999 |
| | NATIONAL ELECTRICAL CODE. PLEASE KNOW THERE HAVE BEEN |
| | TWO CODE CHANGES SINCE THIS 1999 NFPA-70 HAS BEEN IN |
| | EFFECT. THE 1999 EDITION IN THE STATE OF FLORIDA WAS NO |
| | LONGER IN EFFECT AFTER JULY 2003. PLEASE SEE THE LIST |
| | BELOW. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | ** THESE ARE TO BE STATED ON ELECTRICAL PLANS AS WELL |
| | AS COVER SHEET. THE 2003 LS CODE IS ALREADY STATED ON |
| | G1.0. |
| | |
| | 7) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR THE FIRM CASCO PER FLORIDA STATUTES 481.0219 AND |
| | 471.023. MISSING REQUIRED CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR BOTH THE ARCHITECTURAL BUSINESS AND |
| | ENGINEERING BUSINESS. |
| | THIS IS REQUIRED FOR BOTH SERVICES BEING OFFERED. |
| | PLEASE ALSO KNOW THIS IS REQUIRED FOR ALL SHEETS AND |
| | FOR ALL TRADE WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADE REVIEWER(S). |
| | |
| | 8) NOTE: PLEASE VERIFY LOADS AS THE PLANS ON E2.1 SHOWS |
| | A LOAD TOTAL OF 316.9 AMPS ON A PANEL *A* WHICH IS ONLY |
| | RATED 200AMPS. |
| | PLEASE VERIFY THE SERVICE AS NOTED ABOVE THESE PLANS |
| | SHOWS A 200AMP SERVICE ON SHEET E2.1 AND SHEET E4.0 |
| | SHOWS AND MENTIONS 400AMP SERVICE. AS THESE DO NOT |
| | COORDINATE AND THE 200AMP SERVICE AS SHOWN ON E2.1 IS |
| | NOT SUFFICIENT THESE ITEMS WILL BE REQUIRED TO BE |
| | ADJUSTED TO MEET MINIMUM CODE COMPLIANCE. |
| | PLEASE ALSO SUBMIT LOAD CALCULATIONS ON PANEL *B* AS |
| | THE LOADS IS SHOWN AS 100AMPS ON A 100AMPS BREAKER. |
| | PLEASE PROVIDE MORE INFORMATION ON LOAD CALCULATIONS |
| | FOR AL EQUIPMENT. PLEASE VERIFY AND SHOW HEAT LOADS ON |
| | RT UNITS. |
| | PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT PROTECTION |
| | FOR HEAT STRIPS W/ RT UNITS. |
| | PLEASE SEE NEC 220, 215.3, 215.5, 310.16, 240.4 ETC FBC |
| | 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 9) NOTE: PLEASE SEE NO LIGHTING PERFORMANCE |
| | CALCULATIONS WERE SUBMITTED AS REQUIRED PER 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2. PLEASE KNOW ANY CHANGES TO |
| | EXTERIOR LIGHTING SHALL MEET 13-415.2.ABC.1.3. PLEASE |
| | SUBMIT LP CALCULATIONS. AS NONE WERE SUBMITTED AT THIS |
| | TIME MINIMUM CODE COMPLIANCE REVIEW FOR THESE CAN NOT |
| | BE DONE. ** THIS OFFICE CAN NOT EMPHASIZE ENOUGH PLEASE |
| | BE SURE TO SEE THE CODE SECTIONS AS NOTED ABOVEAND |
| | PLEASE BE SURE ALL LIGHTING ON PLANS ARE INCLUDED WITH |
| | THE CALCULATIONS. |
| | |
| | 10) NOTE: PLEASE VERIFY LIGHTING CONTROLS AS REQUIRED |
| | PER 13-415.1.ABC.1.2, .1.3 AND .1.4. |
| | FOR EXAMPLE: |
| | PLEASE KNOW THE EXTERIOR LIGHTS SHALL MEET ONE OF TWO |
| | METHODS OF CONTROL PER 13-415.1.ABC.1.4. AT THIS TIME |
| | PLANS DO NOT INDICATE HOW THE DRIVE THRU LIGHTS ON |
| | CIRCUIT A-26 WILL MEET CODE. |
| | PLEASE KNOW THIS IS ONLY NOTED FOR ONE EXAMPLE AND IS |
| | NOT AN EXHAUSTED LIST. |
| | |
| | 11) NOTE: PLEASE SEE NO TRACK LIGHTING LOADS SHWON PER |
| | 220.43B. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |