| 2008-05-07 14:42:33 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.THIS IS A PLAN REVIEW ONLY.A PERMIT APPLICATION |
| | SIGNED BY A CONTRACTOR LICENSED TO PERFORM THE WORK IS |
| | REQUIRED BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2.THE SHELL BUILDING HAS NOT BEEN ISSUED; THIS IS |
| | REQUIRED FOR A TENANT BUILD OUT PERMIT. |
| | |
| | 3.THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE |
| | OF COMPLETION; IF THE CONTRACTOR FOR THIS TENANT SPACE |
| | IS DIFFERENT FROM THE BASE BUILDING, THEN A LETTER FROM |
| | THE BASE BUILDING CONTRACTOR ALLOWING THE TENANT |
| | BUILDOUT CONTRACTOR TO START WORK ON THIS TENANT SPACE |
| | BEFORE THE C OF C FOR THE BASE BUILDING HAS BEEN ISSUED |
| | WILL BE REQUIRED.THE DEVELOPER AND BOTH CONTRACTORS |
| | WILL BE REQUIRED TO SUBMIT A LETTER STATING THAT THEY |
| | UNDERSTAND THAT ANY DISPUTE OVER RESPONSIBILITY DOES |
| | NOT RELIEVE THEM FROM THE JOINT RESPONSIBILITY TO |
| | COMPLY WITH THE BUILDING CODE. |
| | |
| | 4. G1.0, GOVERNING CODE IS TO INCLUDE 2007 |
| | REVISIONS/SUPPLEMENTS.WWW.FLORIDABUILDING.ORG |
| | |
| | 5. SHOW MANEUVERING CLEARANCE REQUIRED, PULL SIDE, |
| | MEN?S RESTROOM, FBC FIGURE 11-25. |
| | |
| | 6. SEE ATTACHED PARKING DETAIL; PLEASE REVISE PLAN. |
| | C1.1. |
| | |
| | 7. DECLARE TOTAL NUMBER OF PARKING SPACES AND TOTAL |
| | NUMBER OF ACCESSIBLE SPACES, FBC11-4.1.2(5). |
| | |
| | 8. THE ARCHITECT?S TITLE BLOCK STATES THAT THE |
| | PROFESSIONAL OF RECORD IS PRACTICING AS AN INDIVIDUAL. |
| | ALL INFORMATION REQUIRED BY FAC61G1-15 IS REQUIRED ON |
| | EACH SHEET (TITLE BLOCK INFORMATION).A CERTIFICATE OF |
| | AUTHORIZATION IS REQUIRED IF CASCO IS PRACTICING |
| | ARCHITECTURE IN FLORIDA, FS481. |
| | |
| | 9. THE ARCHITECT?S SIGNATURE IS TO BE AN ORIGINAL, |
| | FS481, PER FLORIDA BOARD OF ARCHITECTS. |
| | |
| | 10. PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| | OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| | |
| | 11. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4. |
| | |
| | 12. SEPARATE PERMITS WILL BE REQUIRED FOR SIGNS, |
| | AWNINGS, ETC.INFORMATIONAL ONLY. |
| | |
| | 13. C1.1 SHOWS A DRIVE THROUGH WINDOW.IS THIS |
| | INCLUDED ON THE SHELL PERMIT OR IN THIS PERMIT? |
| | PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL IF |
| | APPLICABLE. |
| | |
| | 14. SHEET A6.0, SEE FBC FIGURE 11-29, 11-31, LAVATORY |
| | CLEARANCES, GRAB BARS AT WATER CLOSETS, AND REVISE |
| | DETAILS INCLUDING MIRROR, TOILET PAPER DISPENSER, . |
| | |
| | |
| | |
| | |
| | |
| | |