| Plan Review Notes For Permit 08040502 |
| Permit Number |
08040502 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-26 07:41:27 | | | | | | | DENIED | | | | | | 1)CORRECT JOB SITE ADDRESS IS REQUIRED ON PERMIT | | | APPLICATION AND IN CONSTRUCTION SERVICES DATA BASE FOR | | | INSPECTIONS AND RECORDS, ADDRESS PROVIDED NOT CORRECT. | | | | | | 2)PROVIDE LAYOUT AND SIZES OF REMAINDER OF WINDOWS IN | | | BUILDING, PLEASE NOTE THAT IF REPLACEMENT OF THE GLAZED | | | AREA EXCEEDS 25% OF THE TOTAL GLAZED AREA IN THE | | | BUILDING OPENING PROTECTION WILL BE REQUIRED FOR THE | | | NEW WINDOWS | | | | | | 3)THE MULLION SIZE OUTLINED IN THE PRODUCT APPROVALS | | | WILL WORK FOR THE VERTICAL MULLION HOWEVER WILL NOT | | | MEET REQUIRED DESIGN PRESSURES FOR THE HORIZONTAL | | | MULLION REQUIRED BETWEEN THE 2 SINGLE HUNG UNITS AND | | | THE FIXED UNIT | | | | | | 4)IF FIXED UNIT IS A HALF ROUND THE HEIGHT WOULD BE | | | APPROX 37" NOT 30" AS STATED PLEASE CONFIRM HEIGHT, | | | ALSO THE REQUIRED DESIGN PRESSURE FOR THE SQUARE | | | FOOTAGE OF THESE OPENINGS IS +33.7 -36.7 PSF THE CHOSEN | | | GLAZING OF THE FIXED UNIT FOR THAT SIZE DOES NOT MEET | | | THIS REQUIREMENT | | | | | | ADRIAN MORSE | | | BLDG PLAN REVIEW | | | 561 805-6716 |
|