Plan Review Notes
Plan Review Notes For Permit 08040475
Permit Number 08040475
Review Stop B
Sequence Number 3
Notes
Date Text
2008-05-28 17:25:263RD
 BUILDING PLAN REVIEW
 PERMIT: 08040475
 ADD: 400 N. FLAGLER DR. #1102
 CONT: OWNER BUILDING ALIANCES INC.
 TEL: (561)433-9020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 5-28-08
 REVIEW: 3RD
 ACTION: DENIED
  
 1) OK
 2) OK
  
 *NOTED: HOWEVER, LEVEL 2 ALTERATION INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT. THE BUILDING IS ABOUT 23 STORIES HIGH
 THEREFORE THE CONSTRUCTION TYPE CANNOT BE TYPE 111 PER
 TABLE 503.
 3)2004 FBC EXISTING: 301.5 THE DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 *NOTED; HOWEVER, THE UL DESIGN NUMBER AND SYSTEM
 REQUIRED*
 4)THE APPLICATION INDICATES THE CAPPING OF BIDET, THE
 REMOVAL OF AN EXISTING SHOWER AND TUB WHICH WILL
 REQUIRE THE FLOOR TO BE SEAL WITH AN APPROVED
 PENETRATION FIRE STOP SYSTEM WHEN THESE ITEMS ARE
 REMOVED. THE RESPONSE LETTER INDICATES THE REMOVAL OF
 THE BIDET PLUMBING; THEREFORE C-AJ-1090 OR C-AJ-1080
 WILL NOT BE APPLICABLE FOR SEALING THE FLOOR WHEN THE
 PIPE IS REMOVED. CHOOSE A DIFFERENT ASSEMBLE FOR
 PATCHING THE FLOOR.
  
 5)NOTED.
 6)NOTED
  
 *NO RESPONSE NOT ADDRESSED*
 7)A CBC CONTRACTOR CANNOT DO ANY STRUCTURAL WORK ON A
 BUILDING OVER THREE STORIES IN HEIGHT. THE FLOOR
 PENETRATIONS REPAIRS SHALL BE PERFORMED BY A LICENSE
 GENERAL CONTRACTOR OR A LICENSE FIRE PROOFING COMPANY.
 INFORMATION SHALL BE PROVIDED TO THIS OFFICE STATING
 WHO WILL BE RESPONSIBLE FOR ALL STRUCTURAL
 PENETRATIONS. PROVIDE THE UL SYSTEM FOR THE FLOOR
 PENETRATIONS ON THE PLANS. THE LETTER FROM THE
 ARCHITECT, WHICH STATES ?PROVIDE 1 HOUR RATED CALKING
 AT FLOOR PENETRARTIONS IS NOT SUFFICIENT INFORMATION
 FOR THE FLOOR ASSEMBLY. A UL ASSEMBLY IS REQUIRED
 MEETING THE EXISTING FLOOR FIRE RATING. ONCE AGAIN, A
 CBC CONTRACTOR IS NOT ALLOWED TO DO ANY STRUCTURAL WORK
 ON BUILDINGS OVER THREE STORIES.
  
 8)NO NEW WALLS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]