| Date |
Text |
| 2008-05-28 17:25:26 | 3RD |
| | BUILDING PLAN REVIEW |
| | PERMIT: 08040475 |
| | ADD: 400 N. FLAGLER DR. #1102 |
| | CONT: OWNER BUILDING ALIANCES INC. |
| | TEL: (561)433-9020 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 5-28-08 |
| | REVIEW: 3RD |
| | ACTION: DENIED |
| | |
| | 1) OK |
| | 2) OK |
| | |
| | *NOTED: HOWEVER, LEVEL 2 ALTERATION INCLUDE THE |
| | RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION |
| | OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION |
| | OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL |
| | EQUIPMENT. THE BUILDING IS ABOUT 23 STORIES HIGH |
| | THEREFORE THE CONSTRUCTION TYPE CANNOT BE TYPE 111 PER |
| | TABLE 503. |
| | 3)2004 FBC EXISTING: 301.5 THE DESIGN PROFESSIONAL OR |
| | AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. |
| | |
| | *NOTED; HOWEVER, THE UL DESIGN NUMBER AND SYSTEM |
| | REQUIRED* |
| | 4)THE APPLICATION INDICATES THE CAPPING OF BIDET, THE |
| | REMOVAL OF AN EXISTING SHOWER AND TUB WHICH WILL |
| | REQUIRE THE FLOOR TO BE SEAL WITH AN APPROVED |
| | PENETRATION FIRE STOP SYSTEM WHEN THESE ITEMS ARE |
| | REMOVED. THE RESPONSE LETTER INDICATES THE REMOVAL OF |
| | THE BIDET PLUMBING; THEREFORE C-AJ-1090 OR C-AJ-1080 |
| | WILL NOT BE APPLICABLE FOR SEALING THE FLOOR WHEN THE |
| | PIPE IS REMOVED. CHOOSE A DIFFERENT ASSEMBLE FOR |
| | PATCHING THE FLOOR. |
| | |
| | 5)NOTED. |
| | 6)NOTED |
| | |
| | *NO RESPONSE NOT ADDRESSED* |
| | 7)A CBC CONTRACTOR CANNOT DO ANY STRUCTURAL WORK ON A |
| | BUILDING OVER THREE STORIES IN HEIGHT. THE FLOOR |
| | PENETRATIONS REPAIRS SHALL BE PERFORMED BY A LICENSE |
| | GENERAL CONTRACTOR OR A LICENSE FIRE PROOFING COMPANY. |
| | INFORMATION SHALL BE PROVIDED TO THIS OFFICE STATING |
| | WHO WILL BE RESPONSIBLE FOR ALL STRUCTURAL |
| | PENETRATIONS. PROVIDE THE UL SYSTEM FOR THE FLOOR |
| | PENETRATIONS ON THE PLANS. THE LETTER FROM THE |
| | ARCHITECT, WHICH STATES ?PROVIDE 1 HOUR RATED CALKING |
| | AT FLOOR PENETRARTIONS IS NOT SUFFICIENT INFORMATION |
| | FOR THE FLOOR ASSEMBLY. A UL ASSEMBLY IS REQUIRED |
| | MEETING THE EXISTING FLOOR FIRE RATING. ONCE AGAIN, A |
| | CBC CONTRACTOR IS NOT ALLOWED TO DO ANY STRUCTURAL WORK |
| | ON BUILDINGS OVER THREE STORIES. |
| | |
| | 8)NO NEW WALLS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |