 BUILDING PLAN REVIEW
 PERMIT: 08040475
 ADD: 400 N. FLAGLER DR. #1102
 CONT: OWNER BUILDING ALIANCES INC.
 TEL: (561)433-9020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-30-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 *NO RESPONSE NOT ADDRESSED*
 2) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT AFTER JULY
 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC BUILDING
 WITH THE 2007 SUPPLEMENTS.
  
 *NO RESPONSE NOT ADDRESSED*
 3)2004 FBC EXISTING
 301.5 THE DESIGN PROFESSIONAL OR AN OWNER MUST ELECT
 ONE OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT
 TO SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 *NOTED; HOWEVER, THE UL DESIGN NUMBER AND SYSTEM
 REQUIRED*
 4)THE APPLICATION INDICATES THE CAPPING OF BIDET, THE
 REMOVAL OF AN EXISTING SHOWER AND TUB WHICH WILL
 REQUIRE THE FLOOR TO BE SEAL WITH AN APPROVED
 PENETRATION FIRE STOP SYSTEM WHEN THESE ITEMS ARE
 REMOVED.
  
 5)NOTED.
  
 *NO RESPONSE NOT ADDRESSED*
 6)712.4.1.2 THROUGH-PENETRATION FIRE STOPS SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRE STOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER. THE SYSTEM SHALL HAVE AN F RATING AND A T RATING
 OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED
 RATING OF THE FLOOR PENETRATED.
  
 *NO RESPONSE NOT ADDRESSED*
 7)A CBC CONTRACTOR CANNOT DO ANY STRUCTURAL WORK ON A
 BUILDING OVER THREE STORIES IN HEIGHT. THE FLOOR
 PENETRATIONS REPAIRS SHALL BE PERFORMED BY A LICENSE
 GENERAL CONTRACTOR OR A LICENSE FIRE PROOFING COMPANY.
 INFORMATION SHALL BE PROVIDED TO THIS OFFICE STATING
 WHO WILL BE RESPONSIBLE FOR ALL STRUCTURAL
 PENETRATIONS. PROVIDE THE UL SYSTEM FOR THE FLOOR
 PENETRATIONS ON THE PLANS.
  
 *NO RESPONSE NO ADDRESSED*
 8)PROVIDE THE DETAILS FOR THE NEW WALL INDICATING ALL
 THE MATERIALS. ANY PENETRATIONS THROUGH A FIRE WALL
 SHALL REPAIR IN A MANNER WHICH MEETS THE RATING OF THE
 EXISTING WALL. THE UL NUMBER FOR FIRE PARTITION WALL
 NEED TO SHOWN ON THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]