| Plan Review Notes For Permit 08040475 |
| Permit Number |
08040475 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-21 13:46:02 | *** PROVISO *** | | | 1) 2004 FBC/R R303.3 BATHROOMS. | | | BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR | | | ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN | | | WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.279 M 2 ), | | | ONE-HALF OF WHICH MUST BE OPENABLE. | | | | | | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE | | | ARTIFICIAL LIGHT AND A MECHANICAL VENTILATION SYSTEM | | | ARE PROVIDED. THE MINIMUM VENTILATION RATES SHALL BE 50 | | | CFM (23.6 L/S) FOR INTERMITTENT VENTILATION OR 20 CFM | | | (9.4 L/S) FOR CONTINUOUS VENTILATION. VENTILATION AIR | | | FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE | | | OUTSIDE. | | | | | | A MECHANICAL PERMIT MAY BE REQUIRED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|