| 2008-04-24 07:39:07 | BUILDING PLAN REVIEW |
| | PERMIT: 08040475 |
| | ADD: 400 N. FLAGLER DR. |
| | CONT: OWNER BUILDING ALIANCES INC. |
| | TEL: (561)433-9020 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 4-23-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 3)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 4)THE APPLICATION INDICATES THE CAPPING OF BIDET, THE |
| | REMOVAL OF AN EXISTING SHOWER AND TUB WHICH WILL |
| | REQUIRE THE FLOOR TO BE SEAL WITH AN APPROVED |
| | PENETRATION FIRE STOP SYSTEM WHEN THESE ITEMS ARE |
| | REMOVED. |
| | |
| | 5)712.4 PENETRATIONS OF A FLOOR, FLOOR/CEILING |
| | ASSEMBLY OR THE CEILING MEMBRANE OF A ROOF/CEILING |
| | ASSEMBLY SHALL BE PROTECTED IN ACCORDANCE WITH SECTION |
| | 707. PENETRATIONS PERMITTED BY EXCEPTIONS 3 AND 4 OF |
| | SECTION 707.2 SHALL COMPLY WITH SECTIONS 712.4.1 |
| | THROUGH 712.4.4 . |
| | |
| | 6)712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED |
| | BY AN APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM |
| | INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR |
| | UL 1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL |
| | OF 0.01 INCH OF WATER. THE SYSTEM SHALL HAVE AN F |
| | RATING AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT |
| | LESS THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. |
| | |
| | 7)A CBC CONTRACTOR CANNOT DO ANY STRUCTURAL WORK ON A |
| | BUILDING OVER THREE STORIES IN HEIGHT. THE FLOOR |
| | PENETRATIONS REPAIRS SHALL BE PERFORMED BY A LICENSE |
| | GENERAL CONTRACTOR OR A LICENSE FIRE PROOFING COMPANY. |
| | INFORMATION SHALL BE PROVIDED TO THIS OFFICE STATING |
| | WHO WILL BE RESPONSIBLE FOR ALL STRUCTURAL |
| | PENETRATIONS. PROVIDE THE UL SYSTEM FOR THE FLOOR |
| | PENETRATIONS ON THE PLANS. |
| | |
| | 8)PROVIDE THE DETAILS FOR THE NEW WALL INDICATING ALL |
| | THE MATERIALS. ANY PENETRATIONS THROUGH A FIRE WALL |
| | SHALL REPAIR IN A MANNER WHICH MEETS THE RATING OF THE |
| | EXISTING WALL. THE UL NUMBER FOR FIRE PARTITION WALL |
| | NEED TO SHOWN ON THE PLANS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |