Plan Review Notes
Plan Review Notes For Permit 08040474
Permit Number 08040474
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-18 14:37:04PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1 IS INDICATING A PROCESSOR AND SHEET P-1
 IS INDICATING THE PROCESSOR BEING TIED INTO THE
 SANITARY SYSTEM. PLEASE KNOW THAT A NEUTRALIZATION TANK
 MAY BE REQUIRED FOR THIS EQUIPMENT PRIOR TO CONNECTION
 TO THE SANITARY SYSTEM.
 PER FBC PLUMBING SECTION 1003.1 WHERE REQUIRED.
 INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO
 PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER
 SUBSTANCES HARMFUL OR HAZARDOUS TO THE BUILDING
 DRAINAGE SYSTEM, THE PUBLIC SEWER, OR SEWAGE TREATMENT
 PLANT OR PROCESSES.
 *PLEASE REFERENCE THE FOLLOWING*
 PER MUNICIPAL CODE ARTICLE III SECTION 90-125(B)
 DISCARGE PROHIBITIONS(20)(D) LOCAL PRETREATMENT
 STANDARDS, TABLE INSET:
 THE PROPOSED PROCESSOR SHALL BE APPROVED BY
 ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY
 DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: (561)
 822-2272, E-MAIL: [email protected]. THE FAX NUMBER IS
 (561) 822-2287. NOTE: WRITTEN APPROVAL IS REQUIRED OF
 THE PROPOSED PROCESSOR FROM ENVIRONMENTAL COMPLIANCE
 BEFORE A PERMIT CAN BE ISSUED.
 PLEASE PROVIDE TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS OF THE PROCESSOR. CLEARLY
 INDICATING THE MAKE MODEL NUMBER AND A LISTING FROM A
 NATIONALL RECOGNIZED TESTING LABORATORY (THIRD PARTY
 TESTING AND CERTIFICATION). PER FBC PLUMBING SECTION
 303.4.
  
 2. SHEET P-1 IS INDICATING THE PROPOSED PROCESSOR
 BEING TIED INTO THE POTABLE WATER SYSTEM. PROTECTION
 AGAINST CONTAMINATION IS REQUIRED PER FBC PLUMBING
 SECTION 608.3 DEVICES, APPURTENANCES, APPLIANCES AND
 APPARATUS.
 ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS
 INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS
 STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER
 SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY
 SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS,
 COMMERCIAL DRINKING WATER DISPENSERS AND ALL OTHER
 APPLIANCES AND DEVICES THAT HANDLE OR TREAT POTABLE
 WATER SHALL BE PROTECTED AGAINST CONTAMINATION.
 PLEASE PROVIDE TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS OF THE PROCESSOR. CLEARLY
 INDICATING THE MAKE MODEL NUMBER AND A LISTING FROM A
 NATIONALL RECOGNIZED TESTING LABORATORY (THIRD PARTY
 TESTING AND CERTIFICATION). PER FBC PLUMBING SECTION
 303.4.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved