| 2008-04-29 15:58:17 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.ON THE PRODUCT APPROVAL, CIRCLE THE ANCHORING |
| | METHOD AND/OR GLASS OPTION YOU PROPOSE TO USE.THIS IS |
| | TO CORRELATE WITH DESIGN CRITERIA WHICH YOU HAVE |
| | SPECIFIED IN YOUR DRAWING.FOR INSTANCE, DESIGN |
| | CRITERIA IS -146 FOR THE OXXO 12080 SGD, BUT SHEET 1 OF |
| | 23 FOR THE PRODUCT APPROVAL STATES THAT ALL DESIGN |
| | PRESSURES FOR 8'0 HIGH PANELS IS -100. |
| | |
| | 2.THE PRODUCT APPROVAL APPEARS INCOMPLETE FOR THE |
| | SLIDING GLASS DOOR.THE STATE APPROVAL REFERS TO A |
| | MIAMIDADE NOA, THE SPEC SHEETS APPEAR TO BE A PART OF A |
| | NOA, NO NOA COVER SHEET AND NOT ENOUGH PAGES SUBMITTED. |
| | |
| | |
| | 3.PLEASE NOTE THAT ENGINEERING MAY BE REQUIRED |
| | DEPENDING ON THE DESIGN PRESSURES USED.FBC1609.IF |
| | PRODUCTS COMPLY WITH THE DESIGN PRESSURES SHOWN ON YOUR |
| | DRAWING, NO ENGINEERING WILL BE RQUIRED (-138.4 TO |
| | -155PSF).HOWEVER, IF YOU REDUCE YOUR DESIGN |
| | PRESSURES, CERTIFICATION BY AN ENGINEER MAY BE |
| | REQUIRED. |