| 2008-04-21 09:02:59 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1. PROVIDE TWO COLLATED IDENTICAL SETS OF PERMIT |
| | DOCUMENTS FOR PERMIT ISSUANCE.IT IS DIFFICULT TO |
| | DETERMINE WHERE ONE PRODUCT APPROVAL STARTS AND ANOTHER |
| | BEGINS.THE PAPERWORK FOR EACH PRODUCT APPROVAL SHOULD |
| | BE STAPLED INDEPENDENTLY.ABOUT 60 LOOSE SHEETS WERE |
| | SUBMITTED.SEE FAC9B72. |
| | |
| | 2. I CANNOT DISCERN FROM THE FLOOR PLAN SCOPE OF WORK. |
| | FOR INSTANCE, ONE STATES |
| | |
| | 4 UNITS |
| | 2-25 SH |
| | 2-34 ? X 63 |
| | |
| | PROVIDE AN OVERALL OPENING SIZE (THIS DETERMINES DESIGN |
| | PRESSURE).SPECIFY WINDOW SIZES. |
| | |
| | 3. SPECIFY ALL WINDOW TYPES.ROOM DESIGNATIONS MAY BE |
| | REQUIRED.SOME WINDOWS STATE SH, OTHERS DO NOT STATE |
| | WINDOW TYPE. |
| | |
| | 4. THE PRODUCT APPROVALS ARE ILLEGIBLE.PLEASE PROVIDE |
| | LEGIBLE PRODUCT APPROVALS.THEY MAY BE AVAILABLE AT |
| | WWW.FLORIDABUILDING.ORG.THE PRODUCT APPROVALS SHOULD |
| | INCLUDE THE FLORIDA STATE COVER SHEET (SHOWS CODE |
| | VERSION, STATUS, ETC.), EVALUATION REPORT AND |
| | INSTALLATION INSTRUCTIONS (ASSOCIATED DOCUMENTATION |
| | WHICH SHOULD BE A LINK OR LINKS FROM THE FLORIDA STATE |
| | PRODUCT APPROVAL). |
| | |