| 2009-01-14 16:00:38 | ** DENIED REVIEW OF REVISIONS** |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.4. THE PLANS |
| | PREVIOUSLY AND STILL CONTAIN NOTES WHICH STATE ALL |
| | OUTSIDE LIGHTING IS TO BE CONTROLLED VIA PHOTO-SENSOR. |
| | HOWEVER THE PLANS NOW CONTAIN A TIME CLOCK. IS THE TIME |
| | CLOCK NOW THE ONLY CONTROL OR IS THE PHOTO-SENSOR ALSO |
| | PART OF THE TIME CLOCK? |
| | IF THE TIME CLOCK IS NOW THE ONLY CONTROL, THEN PER |
| | SECTION ABOVE THIS MUST BE A ASTRONOMICAL TIME CLOCK |
| | WITH A MINIMUM OF 10HR BATTERY BACK UP. THIS WAS |
| | BROUGHT UP ON INITIAL REVIEWS OF THE PROJECT HOWEVER |
| | PLANS WERE REVISED TO NOTE THE PHOTO-SENSORS. |
| | PLEASE VERIFY HOW THESE ARE INDEED CONNECTED. |
| | |
| | 2) NOTE: PLEASE SEE 110.26 AS THE DISCONNECT NOW ON THE |
| | PLANS FOR NEW CONDENSING UNIT DOES NOT MEET MINIMUM |
| | CLEARANCES. |
| | NOT THE SAME ON MECHANICAL PLANS. |
| | 3) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS AS |
| | THERE HAS BEEN AN INCREASE IN LIGHTING FOR EXTERIOR AS |
| | WELL AS INTERIOR LIGHTING. A REVISE FIXTURE LEGEND |
| | SPECIFIC TO ALL FIXTURES IS NEEDED. |
| | THE OTHER ITEM WHICH DOES NOT COORDINATE IS THE |
| | INTERIOR FLUORESCENT FIXTURES WHICH ARE NOTED AS 8FT ON |
| | PLANS AND 4FT ON LEGEND. |
| | PLEASE BE SURE TO SEE 13-415.2,13-415.2.ABC.1.1 AND |
| | .1.2 FOR INTERIOR LIGHTING. |
| | PLEASE BE SURE TO SEE 13-415.2, 13-415.2.ABC.1.3 FOR |
| | EXTERIOR LIGHTING. |
| | |
| | ** KEEP IN MIND THE A/C PLANS NOTES THIS SPACE AS |
| | OFFICE AND OTHER SHEETS STATE WAREHOUSE. THIS DOES |
| | AFFECT CALCULATIONS FOR PERMITTED LIGHTING LEVELS. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |