Plan Review Notes
Plan Review Notes For Permit 08040438
Permit Number 08040438
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-20 15:39:18** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 STATE PREPARED BY MR. AMES BENNETT ARCHITECT HOWEVER
 THE SUBMITTED CALCULATIONS ONLY CONTAIN A SHOP DRAWING
 REVIEW STAMP AND ARE NOT SIGNED, DATED AND SEALED./
 PLEASE SEE13-103.1 FOR RESPONSIBLE DESIGNER WHO SHALL
 SIGN CALCULATIONS AND FOR SCOPE.
  
 ** PLEASE SEE IDR(INPUT DATA REPORT) WHICH HAS LESS
 LIGHTING THAN SHOWN ON PLANS. PLEASE ADJUST.
  
 2) NOTE: PLEASE VERIFY WHERE THE PHOTO-METRICS ARE
 SHOWN FOR NORMAL LEVELS ON STAIRS MEETING THE LIFE
 SAFETY CODE 7.8.1.3, 7.9.2.2. WHERE DID THE WORDING AND
 NUMBERS ADDED CAME FROM WHERE?
  
 ** PLEASE ALSO SEE THE NEW BATTERY BACK UP STAIR LIGHTS
 ARE NOW SHOWING A *10 HOUR* BACK UP.THIS IS NOT A
 CODE VIOLATION ALTHOUGH THE TYPE OF FIXTURES AS STATED
 CAN NOT PRODUCE 10HR BACK UP. THERE WAS NOTHING IN
 PREVIOUS COMMENTS WHICH REQUIRED 10HR BATTERY BACK UP
 FOR THESE STAIR LIGHTS. THE COMMENT HAD TO DO WITH
 10FOOT CANDLES OF LIGHT WHICH WAS REQUIRED.
 PLEASE COORDINATE PLANS, FIXTURES ETC.
  
  
 3) NOTE: PLACED CALL TO MR. TONY ZIA AT 3:18PM ON 6/20
 AND LEFT MESSAGE.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  