| Date |
Text |
| 2008-06-20 15:39:18 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | STATE PREPARED BY MR. AMES BENNETT ARCHITECT HOWEVER |
| | THE SUBMITTED CALCULATIONS ONLY CONTAIN A SHOP DRAWING |
| | REVIEW STAMP AND ARE NOT SIGNED, DATED AND SEALED./ |
| | PLEASE SEE13-103.1 FOR RESPONSIBLE DESIGNER WHO SHALL |
| | SIGN CALCULATIONS AND FOR SCOPE. |
| | |
| | ** PLEASE SEE IDR(INPUT DATA REPORT) WHICH HAS LESS |
| | LIGHTING THAN SHOWN ON PLANS. PLEASE ADJUST. |
| | |
| | 2) NOTE: PLEASE VERIFY WHERE THE PHOTO-METRICS ARE |
| | SHOWN FOR NORMAL LEVELS ON STAIRS MEETING THE LIFE |
| | SAFETY CODE 7.8.1.3, 7.9.2.2. WHERE DID THE WORDING AND |
| | NUMBERS ADDED CAME FROM WHERE? |
| | |
| | ** PLEASE ALSO SEE THE NEW BATTERY BACK UP STAIR LIGHTS |
| | ARE NOW SHOWING A *10 HOUR* BACK UP.THIS IS NOT A |
| | CODE VIOLATION ALTHOUGH THE TYPE OF FIXTURES AS STATED |
| | CAN NOT PRODUCE 10HR BACK UP. THERE WAS NOTHING IN |
| | PREVIOUS COMMENTS WHICH REQUIRED 10HR BATTERY BACK UP |
| | FOR THESE STAIR LIGHTS. THE COMMENT HAD TO DO WITH |
| | 10FOOT CANDLES OF LIGHT WHICH WAS REQUIRED. |
| | PLEASE COORDINATE PLANS, FIXTURES ETC. |
| | |
| | |
| | 3) NOTE: PLACED CALL TO MR. TONY ZIA AT 3:18PM ON 6/20 |
| | AND LEFT MESSAGE. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |