| 2008-05-01 11:13:13 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE OUTSIDE AIR CALCULATIONS ON PLANS SHOWING |
| | OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, VOLUME OF |
| | OUTSIDE AIR REQUIRED AND VOLUME OF OUTSIDE AIR PROVIDED |
| | IN ACCORDANCE WITH FBCM TABLE 403.3. |
| | |
| | 2. A RESIDENTIAL MANUAL J LOAD CALCULATION HAS BEEN |
| | PROVIDED FOR THIS PROJECT. THIS IS NOT RESIDENTIAL |
| | CONSTRUCTION. A COOLING LOAD CALCULATION SHALL BE |
| | PERFORMED FOR NEWLY INSTALLED UNITS AS PER CRITERIA OF |
| | SECTION 3.1 OF APPENDIX 13-B OF THIS CHAPTER. THIS |
| | CALCULATION SHALL BE ATTACHED TO THE CODE COMPLIANCE |
| | FORM SUBMITTED TO THE BUILDING DEPARTMENT WHEN THE |
| | BUILDING IS PERMITTED IN ACCORDANCE WITH FBCB |
| | 13-407.1.ABC.1. COOLING SYSTEM DESIGN LOADS, FOR THE |
| | PURPOSE OF SIZING HVAC SYSTEMS AND EQUIPMENT, SHALL BE |
| | DETERMINED IN ACCORDANCE WITH ONE OF THE PROCEDURES |
| | DESCRIBED IN CHAPTER 26 OF THE ASHRAE HANDBOOK OF |
| | FUNDAMENTALS OR ACCA MANUAL N, COMMERCIAL LOAD |
| | CALCULATION IN ACCORDANCE WITH FBCB CHAPTER 13 APPENDIX |
| | B SECTION 3.1.1. |
| | |
| | 3. PAGE 3 SHOWS AN ALUMINUM PRE-ENGINEERED A/C STAND. |
| | THIS IS A STRUCTURAL COMPONENT AS DEFINED IN FAC RULE |
| | 9B-72. THEREFORE A PRODUCT APPROVAL IS REQUIRED. THE |
| | PRODUCT APPROVAL SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD FOR THIS PROJECT AND |
| | SUBMITTED TO THIS OFFICE IN ACCORDANCE WITH FBCB |
| | 106.3.3. |
| | |
| | 4. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN |
| | ACCORDANCE WITH FBCM 307.2.1 AND MEANS OF AUXILIARY OR |
| | SECONDARY DRAIN PROTECTION IN ACCORDANCE WITH FBCM |
| | 307.2.3. |
| | |
| | 5. PROVIDE SHUTOFF DAMPER CONTROL AT OUTSIDE AIR |
| | INTAKE. OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL BE |
| | EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY |
| | SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE |
| | IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3. A GRAVITY |
| | OPERATED DAMPER IS ACCEPTABLE IN A SYSTEM WITH A DESIGN |
| | OUTSIDE AIR INTAKE CAPACITY OF 300 CFM OR LESS IN |
| | ACCORDANCE WITH EXCEPTION #2 OF THIS SECTION. |
| | |
| | 6. ENERGY CALCULATIONS: THE CERTIFICATION PAGE IS NOT |
| | SIGNED BY THE PERSON WHO PREPARED THE ENERGY |
| | CALCULATIONS. THE PERSON PREPARING THE COMPLIANCE |
| | CALCULATION SHALL CERTIFY THAT THE PLANS AND |
| | SPECIFICATIONS COVERED BY THE CALCULATION, OR |
| | AMENDMENTS THERETO, ARE IN COMPLIANCE WITH CHAPTER 13 |
| | OF THE FLORIDA BUILDING CODE IN ACCORDANCE WITH FBCB |
| | 13-103.1.1. |
| | |
| | 7. ENERGY CALCULATIONS: THE BUILDING?S OWNER/AGENT HAS |
| | NOT SIGNED THE ENERGY CALCULATIONS ON THE |
| | CERTIFICATIONS PAGE. THE BUILDING?S OWNER, THE OWNER?S |
| | ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED |
| | BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN |
| | COMPLIANCE WITH THE CODE, AS PER SECTION 553.907, |
| | FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO |
| | BEGIN CONSTRUCTION OR RENOVATION IN ACCORDANCE WITH |
| | FBCB 13-103.1.2. |
| | |