Plan Review Notes
Plan Review Notes For Permit 08040438
Permit Number 08040438
Review Stop M
Sequence Number 1
Notes
Date Text
2008-05-01 11:13:13REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS ON PLANS SHOWING
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, VOLUME OF
 OUTSIDE AIR REQUIRED AND VOLUME OF OUTSIDE AIR PROVIDED
 IN ACCORDANCE WITH FBCM TABLE 403.3.
  
 2. A RESIDENTIAL MANUAL J LOAD CALCULATION HAS BEEN
 PROVIDED FOR THIS PROJECT. THIS IS NOT RESIDENTIAL
 CONSTRUCTION. A COOLING LOAD CALCULATION SHALL BE
 PERFORMED FOR NEWLY INSTALLED UNITS AS PER CRITERIA OF
 SECTION 3.1 OF APPENDIX 13-B OF THIS CHAPTER. THIS
 CALCULATION SHALL BE ATTACHED TO THE CODE COMPLIANCE
 FORM SUBMITTED TO THE BUILDING DEPARTMENT WHEN THE
 BUILDING IS PERMITTED IN ACCORDANCE WITH FBCB
 13-407.1.ABC.1. COOLING SYSTEM DESIGN LOADS, FOR THE
 PURPOSE OF SIZING HVAC SYSTEMS AND EQUIPMENT, SHALL BE
 DETERMINED IN ACCORDANCE WITH ONE OF THE PROCEDURES
 DESCRIBED IN CHAPTER 26 OF THE ASHRAE HANDBOOK OF
 FUNDAMENTALS OR ACCA MANUAL N, COMMERCIAL LOAD
 CALCULATION IN ACCORDANCE WITH FBCB CHAPTER 13 APPENDIX
 B SECTION 3.1.1.
  
 3. PAGE 3 SHOWS AN ALUMINUM PRE-ENGINEERED A/C STAND.
 THIS IS A STRUCTURAL COMPONENT AS DEFINED IN FAC RULE
 9B-72. THEREFORE A PRODUCT APPROVAL IS REQUIRED. THE
 PRODUCT APPROVAL SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD FOR THIS PROJECT AND
 SUBMITTED TO THIS OFFICE IN ACCORDANCE WITH FBCB
 106.3.3.
  
 4. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBCM 307.2.1 AND MEANS OF AUXILIARY OR
 SECONDARY DRAIN PROTECTION IN ACCORDANCE WITH FBCM
 307.2.3.
  
 5. PROVIDE SHUTOFF DAMPER CONTROL AT OUTSIDE AIR
 INTAKE. OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL BE
 EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY
 SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE
 IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3. A GRAVITY
 OPERATED DAMPER IS ACCEPTABLE IN A SYSTEM WITH A DESIGN
 OUTSIDE AIR INTAKE CAPACITY OF 300 CFM OR LESS IN
 ACCORDANCE WITH EXCEPTION #2 OF THIS SECTION.
  
 6. ENERGY CALCULATIONS: THE CERTIFICATION PAGE IS NOT
 SIGNED BY THE PERSON WHO PREPARED THE ENERGY
 CALCULATIONS. THE PERSON PREPARING THE COMPLIANCE
 CALCULATION SHALL CERTIFY THAT THE PLANS AND
 SPECIFICATIONS COVERED BY THE CALCULATION, OR
 AMENDMENTS THERETO, ARE IN COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BUILDING CODE IN ACCORDANCE WITH FBCB
 13-103.1.1.
  
 7. ENERGY CALCULATIONS: THE BUILDING?S OWNER/AGENT HAS
 NOT SIGNED THE ENERGY CALCULATIONS ON THE
 CERTIFICATIONS PAGE. THE BUILDING?S OWNER, THE OWNER?S
 ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION IN ACCORDANCE WITH
 FBCB 13-103.1.2.
  