2008-05-16 15:43:01***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, PARKING
 GARAGES TO COMPLY WITH THE REQUIREMENTS OF NFPA 88A
 WITH REGARD TO (2) HOUR SEPARATION TO OTHER AREAS.
  
 2) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 4) PLEASE IDENTIFY THE OCCUPANCY CLASSIFICATION(S) PER
 NFPA 101.
  
 5) STAIRS TO COMPLY WITH NFPA 101, SECTION 7.2.2.
  
 6) PLEASE SHOW ADRESS NEW, OR EXISTING ON BUILDING THAT
 SHALL BE MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND
 CONTRASTING WITH BACKGROUND. FULL ADDRESS TO BE
 DISPLAYED IN TITLE BLOCK OF EACH SHEET.
  
 7) SHEET E-1 ILLUSTRATES SMOKE DETECTORS, DEVICES THAT
 ARE TIED INTO A FIRE ALARM SYSTEM. IF A FIRE ALARM
 SYSTEM IS PRESENT, PLEASE ADVISE OR CHANGE THE DEVICE
 IDENTIFICATION TO SMOKE ALARMS.
  
 8) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL. AN ATTACHED SHEET WAS NOT FOUND
 SHOWING THE FIRE SPRINKLER LAYOUT AS INDICATED ON SHEET
 2.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW