| Plan Review Notes For Permit 08040438 |
| Permit Number |
08040438 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-16 15:43:01 | ***DENIED*** | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, PARKING | | | GARAGES TO COMPLY WITH THE REQUIREMENTS OF NFPA 88A | | | WITH REGARD TO (2) HOUR SEPARATION TO OTHER AREAS. | | | | | | 2) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR | | | HANDRAILS. | | | | | | 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 4) PLEASE IDENTIFY THE OCCUPANCY CLASSIFICATION(S) PER | | | NFPA 101. | | | | | | 5) STAIRS TO COMPLY WITH NFPA 101, SECTION 7.2.2. | | | | | | 6) PLEASE SHOW ADRESS NEW, OR EXISTING ON BUILDING THAT | | | SHALL BE MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND | | | CONTRASTING WITH BACKGROUND. FULL ADDRESS TO BE | | | DISPLAYED IN TITLE BLOCK OF EACH SHEET. | | | | | | 7) SHEET E-1 ILLUSTRATES SMOKE DETECTORS, DEVICES THAT | | | ARE TIED INTO A FIRE ALARM SYSTEM. IF A FIRE ALARM | | | SYSTEM IS PRESENT, PLEASE ADVISE OR CHANGE THE DEVICE | | | IDENTIFICATION TO SMOKE ALARMS. | | | | | | 8) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | | SPRINKLER REMODEL. AN ATTACHED SHEET WAS NOT FOUND | | | SHOWING THE FIRE SPRINKLER LAYOUT AS INDICATED ON SHEET | | | 2. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|