| 2008-04-25 15:10:10 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE RELEVANT CODES ARE STATED |
| | ON PLANS. |
| | PLEASE SEE THE FOLLOWING WHICH ARE LISTED ARE TO BE |
| | SHOWN ON ELECTRICAL SHEETS AT A MINIMUM. |
| | NFPA-70 |
| | NFPA-101 |
| | NFPA-72 (WHERE APPLICABLE) |
| | |
| | 2) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND ON PLANS |
| | FOR ALL FIXTURES, TYPES AND INPUT WATTAGES ON PLANS. |
| | PLEASE BE SURE TO SEE THE FOLLOWING COMMENT WHICH HAS |
| | DIRECT RELEVANCY. |
| | FBC 106.1.2, 106.3.5.1.2, FBC CHAPTER 13. |
| | |
| | 3) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | NEED TO BE COMPLETED AND COORDINATE WITH THE PLANS. |
| | PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE |
| | CALCULATIONS REQUIRED. PLEASE SEE 13-415.2.ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED AS IDR |
| | FOR THE REMAINDER OF THIS COMMENT. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE IDR WHICH INDICATES NO EXTERIOR |
| | LIGHTING. HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY |
| | SHOW EXTERIOR LIGHTING? |
| | FOR EXAMPLE: |
| | PLEASE EXPLAIN WHAT FIXTURES ARE THE 1 WATT FIXTURES AS |
| | SHOWN ON THE IDR. THE PLANS DO NOT INDICATE THESE 1 |
| | WATT FIXTURES AS ENTERED. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE METHOD OF CONTROL ON THE IDR IS SHOWN AS |
| | *MANUAL ON/OFF*. HOW IS THIS POSSIBLE WHEN THE PLANS |
| | CLEARLY SHOW THE METHOD OF CONTROL AS AUTOMATED AS |
| | REQUIRED PER 13-415.1.ABC.1.1, .1.2, AND .1.3. |
| | PLEASE SEE THE FIXTURES ON PLANS, FIXTURE LEGEND ETC |
| | AND VERIFY THESE FIXTURES AND WATTAGES AS NOTED ABOVE. |
| | THIS IS BEING EMPHASIZED ONCE AGAIN AS THIS IS ON OF |
| | THE LEADING FAILURE ITEMS FOR NON-ISSUANCE OF PERMIT |
| | FOR CONSTRUCTION. |
| | PLEASE SEE THE METHOD *A* SUBMITTED IS FOR WHOLE |
| | BUILDING COMPLIANCE. HOW IS THIS POSSIBLE WHEN ALL |
| | COMPONENTS ARE NOT ENTERED? |
| | PLEASE SEE 13-400.3.A, 13-400.3.B AND 13-400.3.C WHICH |
| | GIVE YOU INFORMATION ON WHICH VERSION MAY BE USED OR |
| | WHICH VERSION MAY NOT BE USED. |
| | ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES |
| | WITH RESPECT TO METHOD OF CALCULATIONS AND VERSION. |
| | ** PLEASE BE SURE THE SIGNATURE OF THE RESPONSIBLE |
| | DESIGNER IS ALSO ON THE CERTIFICATION SHEETS. THE |
| | INITIALS ARE NOT ACCEPTABLE. FBC 13-101 PLEASE ADJUST. |
| | |
| | |
| | ** THIS ARE SOME EXAMPLES AND IS NOT AN EXHAUSTED LIST |
| | OF ITEMS ON PLANS NOT COMPLETE AND ITEMS ON PLANS WHICH |
| | DO NOT COORDINATE WITH THE IDR AND ENERGY |
| | CALCULATIONS. |
| | |
| | 4) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED |
| | METHOD OF CONTROLS FOR EXTERIOR LIGHTS. |
| | |
| | 5) NOTE: PLEASE SEE THAT *NO* HAND DRAWN CHANGES ARE |
| | PERMITTED TO PLANS. |
| | PLANS ARE ALSO SIGNED DATED AND SEALED BY AN ARCHITECT. |
| | THE CHANGES MADE TO ALL PANELS IN PEN ARE NOT |
| | PERMITTED. |
| | FS 481.221 |
| | |
| | 6) NOTE: PLEASE LABEL ALL PANELS FOR IDENTIFICATION. |
| | EXAMPLE: PANEL A, B ETC |
| | PLEASE SEE THE SUB PANEL FED FROM THE PRIMARY PANEL IS |
| | SHOWN AS 80AMP ON RISER WHICH WAS CHANGED FROM WAS |
| | PRINTED AS 60AMP. PLEASE ALSO SEE THE PRIMARY PANEL |
| | SHOWS 60AMP BREAKER. |
| | PLEASE COORDINATE ALL PANELS. |
| | 230.2E, 408.4 ETC |
| | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND |
| | ADDITIONAL INFORMATION. |
| | |
| | 7) NOTE: PLEASE SUBMIT AND SHOW PHOTO-METRICS MEETING |
| | MINIMUM COMPLIANCE WITH THE 2003 LIFE SAFETY CODE/ |
| | NFPA-101 SECTIONS 7.8.1.3 AND 7.9.2.2 |
| | |
| | 8) NOTE: PLEASE BE SURE THE TITLE BLOCKS REFLECT THE |
| | ADDRESS OF THE PROPOSED SCOPE OF WORK. PLEASE SEE THE |
| | ADDRESS AS APPLIED IS 420 6TH STREET. |
| | PLEASE ADJUST |
| | FBC 106.5, FAC 61G1-16.004 |
| | |
| | 9) NOTE: PLEASE SHOW HOW LIGHTING FROM FIRST FLOOR TO |
| | SECOND FLOOR WILL BE CONTROLLED. |
| | LS 101 7.8 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |