2008-04-25 15:10:10** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE RELEVANT CODES ARE STATED
 ON PLANS.
 PLEASE SEE THE FOLLOWING WHICH ARE LISTED ARE TO BE
 SHOWN ON ELECTRICAL SHEETS AT A MINIMUM.
 NFPA-70
 NFPA-101
 NFPA-72 (WHERE APPLICABLE)
  
 2) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND ON PLANS
 FOR ALL FIXTURES, TYPES AND INPUT WATTAGES ON PLANS.
 PLEASE BE SURE TO SEE THE FOLLOWING COMMENT WHICH HAS
 DIRECT RELEVANCY.
 FBC 106.1.2, 106.3.5.1.2, FBC CHAPTER 13.
  
 3) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 NEED TO BE COMPLETED AND COORDINATE WITH THE PLANS.
 PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE
 CALCULATIONS REQUIRED. PLEASE SEE 13-415.2.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED AS IDR
 FOR THE REMAINDER OF THIS COMMENT.
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH INDICATES NO EXTERIOR
 LIGHTING. HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY
 SHOW EXTERIOR LIGHTING?
 FOR EXAMPLE:
 PLEASE EXPLAIN WHAT FIXTURES ARE THE 1 WATT FIXTURES AS
 SHOWN ON THE IDR. THE PLANS DO NOT INDICATE THESE 1
 WATT FIXTURES AS ENTERED.
 FOR EXAMPLE:
 PLEASE SEE THE METHOD OF CONTROL ON THE IDR IS SHOWN AS
 *MANUAL ON/OFF*. HOW IS THIS POSSIBLE WHEN THE PLANS
 CLEARLY SHOW THE METHOD OF CONTROL AS AUTOMATED AS
 REQUIRED PER 13-415.1.ABC.1.1, .1.2, AND .1.3.
 PLEASE SEE THE FIXTURES ON PLANS, FIXTURE LEGEND ETC
 AND VERIFY THESE FIXTURES AND WATTAGES AS NOTED ABOVE.
 THIS IS BEING EMPHASIZED ONCE AGAIN AS THIS IS ON OF
 THE LEADING FAILURE ITEMS FOR NON-ISSUANCE OF PERMIT
 FOR CONSTRUCTION.
 PLEASE SEE THE METHOD *A* SUBMITTED IS FOR WHOLE
 BUILDING COMPLIANCE. HOW IS THIS POSSIBLE WHEN ALL
 COMPONENTS ARE NOT ENTERED?
 PLEASE SEE 13-400.3.A, 13-400.3.B AND 13-400.3.C WHICH
 GIVE YOU INFORMATION ON WHICH VERSION MAY BE USED OR
 WHICH VERSION MAY NOT BE USED.
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES
 WITH RESPECT TO METHOD OF CALCULATIONS AND VERSION.
 ** PLEASE BE SURE THE SIGNATURE OF THE RESPONSIBLE
 DESIGNER IS ALSO ON THE CERTIFICATION SHEETS. THE
 INITIALS ARE NOT ACCEPTABLE. FBC 13-101 PLEASE ADJUST.
  
  
 ** THIS ARE SOME EXAMPLES AND IS NOT AN EXHAUSTED LIST
 OF ITEMS ON PLANS NOT COMPLETE AND ITEMS ON PLANS WHICH
 DO NOT COORDINATE WITH THE IDR AND ENERGY
 CALCULATIONS.
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED
 METHOD OF CONTROLS FOR EXTERIOR LIGHTS.
  
 5) NOTE: PLEASE SEE THAT *NO* HAND DRAWN CHANGES ARE
 PERMITTED TO PLANS.
 PLANS ARE ALSO SIGNED DATED AND SEALED BY AN ARCHITECT.
 THE CHANGES MADE TO ALL PANELS IN PEN ARE NOT
 PERMITTED.
 FS 481.221
  
 6) NOTE: PLEASE LABEL ALL PANELS FOR IDENTIFICATION.
 EXAMPLE: PANEL A, B ETC
 PLEASE SEE THE SUB PANEL FED FROM THE PRIMARY PANEL IS
 SHOWN AS 80AMP ON RISER WHICH WAS CHANGED FROM WAS
 PRINTED AS 60AMP. PLEASE ALSO SEE THE PRIMARY PANEL
 SHOWS 60AMP BREAKER.
 PLEASE COORDINATE ALL PANELS.
 230.2E, 408.4 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
  
 7) NOTE: PLEASE SUBMIT AND SHOW PHOTO-METRICS MEETING
 MINIMUM COMPLIANCE WITH THE 2003 LIFE SAFETY CODE/
 NFPA-101 SECTIONS 7.8.1.3 AND 7.9.2.2
  
 8) NOTE: PLEASE BE SURE THE TITLE BLOCKS REFLECT THE
 ADDRESS OF THE PROPOSED SCOPE OF WORK. PLEASE SEE THE
 ADDRESS AS APPLIED IS 420 6TH STREET.
 PLEASE ADJUST
 FBC 106.5, FAC 61G1-16.004
  
 9) NOTE: PLEASE SHOW HOW LIGHTING FROM FIRST FLOOR TO
 SECOND FLOOR WILL BE CONTROLLED.
 LS 101 7.8
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  