2008-04-24 11:27:45BUILDING PLAN REVIEW
 PERMIT: 08040438
 ADD: 420 6TH ST
 CONT: BENNARD SIMPSON G C
 TEL: (561) 296-5858
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)VERTICAL ADDITIONS: PLANS SUBMITTED FOR PERMIT
 (FIRST TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE
 REVIEWED TO THE 2004 FBC BUILDING EXISTING BUILDING
 CODE CHAPTER 9 WITH THE2007 SUPPLEMENTS.
 PLEASE UP DATE CODE SUMMARY SHEET.
  
 2) PLEASE NOTE THIS BUILDING IS TO BE CONSIDERED A
 MIXED OCCUPANCY. PLEASE REVIEW 406.2.7 FBC MIXED
 SEPERATION. PARKING GARAGES SHALL BE SEPERATED FROM
 OTHER OCCUPANCIES IN ACCORDANCE WITH SECTION 302.3.2
 AND TABLE 302.3.2.
  
 2A) 1ST FLOOR ENCLOSED PARKING GARAGE VS OFFICE AREA
 WILL REQUIRE A 2 HR SEPERATION SEE TABLE 302.3.2. THIS
 AREA DOES NOT COUNT AS A INCIDENTAL AREA SINCE THE SQ
 FT AREA IS OVER THE ALLOWED 10% OF THE FIRST FLOOR
 AREA. PLEASE PROVIDE WALL AND OPENING PROTECTIVE
 PROTECTION. NOTE TO TAKE THE 1 HOUR REDUCTION ( TABLE
 302.1.1) ALLOWED IN INCIDENTAL AREAS AGAIN THE OFFICE
 AREA WOULD NEED TO BE LESS THAN10% OF THE FIRST FLOOR
 AREA.
  
 2B) ALSO NOTE THAT THE ENCLOSED PARKING GARARE WILL
 REQUIRE OCCUPANCY SEPERATION FROM THE 2ND FLOOR
 OCCUPANCY PLEASE REVIEW 711.3 FBC. THIS WILL ALSO
 INCLUDE THE COLUMNS HOLDING UP THE SECOND STORY.
 SECTION 302.3.2 EXCEPTION WILL ALLOW FOR A 1HR
 REDUCTION FOR THE BUILDING BEING EQUIPPED WITH A FIRE
 SPRINKLER SYSTEM. PLANS INDICATE THAT THE EXISTING
 BUILDING IS ALREADY FIRE SPRINKLERED AND THE SECOND
 STORY WILL BE FIRE SPRINKLERED,THE DESIGN TO BY
 OTHERS AND NOT PART OF THIS PERMIT. NO HOURLY
 REDUCTIONS CAN BE TAKEN IF THE FIRE SPRINKLER PLANS ARE
 NOT SUBMITTED WITH THE ADDITION PERMIT SET. NOTE THE
 FIRE SPRINKLER PLANS WILL ALSO REQUIRE SEPERATE PERMIT
 WITH THERE OWN PLANS.
  
 2C) THE SECOND STORY OCCUPANCIES, CONSIST OF ALSO MIXED
 USE BEING A OFFICE (BUSSINESS) AND WAREHOUSE (
 OCCUPANCY UNKNOWN). THE OFFICE ALO BEING OVER 10% OF
 THE 2ND FLOOR AREA, (NOT QUALIFYING AS A ANSILLARY USE)
 REQUIRING WALL RATINGS AS PER TABLE 302.3.2.
  
 2D) 2ND STORY WAREHOUSE USE AREA, PLEASE PROVIDE WHAT
 TYPE OF GOODS ARE TO BE STORED AND THE QUANITIES OF
 THESE GOODS. EACH AREA OF A BUILDING WITH MULITPLE USE
 AREAS EACH SHALL BE CLASSIFIED
 ACCORDING TO SECTION 302.3.2. WITH NOT HAVING THE
 WAREHOUSE OCCUPANCY KNOWN WE MAY HAVE ADDITIONAL
 COMMENTS AND OR RATINGS PERTAINING TO THE OCCUPANCNCY
 UES. 106.1.2 ADDITIONAL INFORMATION REQUIRED. PLANS DO
 NOT INDICATE THE STORAGE OF ANY FLAMMABLE LIQUIDS
 (GASOLINE)?
  
 3) THE SECOND FLOOR BEING A WAREHOUSE AND LIVE LOAD OF
 125 LBS- SQ FT LOADING:
 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. IT
 SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F
 OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR
 LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER
 SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART OF
 A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS
 PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE
 BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE.
 SUCH PLATES SHALL NOT BE REMOVEDOR DEFACED, & IF
 LOST, REMOVED THE OWNER OF THE BUILDING SHALL REPLACE
 THEM.
  
 4) EXISTING BUILDING CODE 906.1 THE MINIMUM
 REQUIREMENTS. ADDITIONS TO EXISTING BUILDING OR
 STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THE FLORIDA BUILDING CODE BUILDING.
 SUBMITTEDARE MANUAL J OR RESIDENTIAL HVAC FOR
 COMMERCIAL PLEASE USE MANUAL N. ADDITIONAL COMMENTS MAY
 APPEAR WITH THE CORRECT VERSION OF ENERGY CALCS.
  
 5)THE FIRST FLOOR IS A ENCLOSED PARKING GARAGE AND
 WILL NEED TO MEET THE REQUIREMENTS OF 406.4
 FBC-MECHANICAL FOR VENTILATION.
  
 6)NEITHER SHEET 3 NOR 3A INDICATES THE USAGE OF THE
 ROOM. 106.1.2. ADDITIONAL INFO. PLANS WILL NEED TO SHOW
 THE HOW MANY SQ FT ARE GOING TO BE OFFICE AND LAYOUT OF
 OFFICE, THIS MAY ENACT
 ACCESSIBILITY ISSUES.
  
 7) SHEET A4 & A5 BOTH INDICATE ROOF PLANS BUT NEITHER
 PLANS INDICATES ROOF DRAINAGE, THE NEW UPPER ROOF RUNS
 OFF ON TO THE LOWER ROOF BUT THE PLANS DO NOT PROVIDE
 HOW THE WATER WILL BE REMOVED FROM THE LOWER ROOF AREA?
 ROOF DRAINS WITH SECONDARY OVER FLOWS OR THROUGH THE
 WALL SCUPPERS? 1504.3.
  
 8) PLEASE PROVIDE INFORMATION ON THE R-VALUE OF
 INSULATION TO BE PLACED AT THE ROOF? DETAIL A OF SHEET
 5 INDICATES A WOD FRAME WALL INSULATED BUT THE AREA
 ABOVE THE CEILING AND BELOW THE INSULATION AT THE ROOF
 LEVEL IS MISSING INSULATION. PLEASE PROVIDE INSULATION
 IN THIS AREA, IT APPEARS TO BE PART OF THE A/C
 SPACE.13-402.1.A
  
 9) . SHEET A5 CUT SECTIONS DIDN'T INDICATE FLOOR
 INSULATION ON THE AIR CONDITIONED SECOND FLOOR, THIS
 WILL NEED TO MEET EITHER 13-405.1.AB.1 WHERE THERE ARE
 TRADE OFFS UNDER THE ENERGY CODE COMPLIANCE FORMS,
 PLEASE UPDATE THE ENERGY FORMS WITH THECOMMERCIAL
 FORM.
  
 10)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROOFING ASSEMBLIES
 B) TRUSS ANCHORS AND OR STRAPS
  
 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 12)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 13) CLOTH OR CANVAS AWNINGS: A LETTER FROM THE OWNER
 (NOT TENANT) IS TO ACCOMPANY ALLFABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO ACKNOWLEDGE
 THEIR RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED
 PRIOR TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF
 75 MPH OR GREATER. THE LETTER MUST BE SIGNED BY THE
 OWNER NOT TENANT.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH.
  
 14) GUARDRAILS AT THE PARAPET PLEASE PROVIDE HOW
 ATTACHMENT TO THE EXISTING BUILDING WILL BE COMPLETED
 WITH COMPLIANCE TO: 1607.7.1.1 CONCENTRATED LOAD.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST
 A SINGLE CONCENTRATED LOAD OF 200 POUNDS (0.89 KN),
 APPLIED IN ANY DIRECTION AT ANY POINT ALONG THE TOP,
 AND HAVE ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO
 TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL
 ELEMENTS OF THE BUILDING. THIS LOAD NEED NOT BE ASSUMED
 TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN THE
 PRECEDING PARAGRAPH.
  
 15) BUILDING PROVISO:
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved