| 2008-04-24 11:27:45 | BUILDING PLAN REVIEW |
| | PERMIT: 08040438 |
| | ADD: 420 6TH ST |
| | CONT: BENNARD SIMPSON G C |
| | TEL: (561) 296-5858 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E)VERTICAL ADDITIONS: PLANS SUBMITTED FOR PERMIT |
| | (FIRST TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE |
| | REVIEWED TO THE 2004 FBC BUILDING EXISTING BUILDING |
| | CODE CHAPTER 9 WITH THE2007 SUPPLEMENTS. |
| | PLEASE UP DATE CODE SUMMARY SHEET. |
| | |
| | 2) PLEASE NOTE THIS BUILDING IS TO BE CONSIDERED A |
| | MIXED OCCUPANCY. PLEASE REVIEW 406.2.7 FBC MIXED |
| | SEPERATION. PARKING GARAGES SHALL BE SEPERATED FROM |
| | OTHER OCCUPANCIES IN ACCORDANCE WITH SECTION 302.3.2 |
| | AND TABLE 302.3.2. |
| | |
| | 2A) 1ST FLOOR ENCLOSED PARKING GARAGE VS OFFICE AREA |
| | WILL REQUIRE A 2 HR SEPERATION SEE TABLE 302.3.2. THIS |
| | AREA DOES NOT COUNT AS A INCIDENTAL AREA SINCE THE SQ |
| | FT AREA IS OVER THE ALLOWED 10% OF THE FIRST FLOOR |
| | AREA. PLEASE PROVIDE WALL AND OPENING PROTECTIVE |
| | PROTECTION. NOTE TO TAKE THE 1 HOUR REDUCTION ( TABLE |
| | 302.1.1) ALLOWED IN INCIDENTAL AREAS AGAIN THE OFFICE |
| | AREA WOULD NEED TO BE LESS THAN10% OF THE FIRST FLOOR |
| | AREA. |
| | |
| | 2B) ALSO NOTE THAT THE ENCLOSED PARKING GARARE WILL |
| | REQUIRE OCCUPANCY SEPERATION FROM THE 2ND FLOOR |
| | OCCUPANCY PLEASE REVIEW 711.3 FBC. THIS WILL ALSO |
| | INCLUDE THE COLUMNS HOLDING UP THE SECOND STORY. |
| | SECTION 302.3.2 EXCEPTION WILL ALLOW FOR A 1HR |
| | REDUCTION FOR THE BUILDING BEING EQUIPPED WITH A FIRE |
| | SPRINKLER SYSTEM. PLANS INDICATE THAT THE EXISTING |
| | BUILDING IS ALREADY FIRE SPRINKLERED AND THE SECOND |
| | STORY WILL BE FIRE SPRINKLERED,THE DESIGN TO BY |
| | OTHERS AND NOT PART OF THIS PERMIT. NO HOURLY |
| | REDUCTIONS CAN BE TAKEN IF THE FIRE SPRINKLER PLANS ARE |
| | NOT SUBMITTED WITH THE ADDITION PERMIT SET. NOTE THE |
| | FIRE SPRINKLER PLANS WILL ALSO REQUIRE SEPERATE PERMIT |
| | WITH THERE OWN PLANS. |
| | |
| | 2C) THE SECOND STORY OCCUPANCIES, CONSIST OF ALSO MIXED |
| | USE BEING A OFFICE (BUSSINESS) AND WAREHOUSE ( |
| | OCCUPANCY UNKNOWN). THE OFFICE ALO BEING OVER 10% OF |
| | THE 2ND FLOOR AREA, (NOT QUALIFYING AS A ANSILLARY USE) |
| | REQUIRING WALL RATINGS AS PER TABLE 302.3.2. |
| | |
| | 2D) 2ND STORY WAREHOUSE USE AREA, PLEASE PROVIDE WHAT |
| | TYPE OF GOODS ARE TO BE STORED AND THE QUANITIES OF |
| | THESE GOODS. EACH AREA OF A BUILDING WITH MULITPLE USE |
| | AREAS EACH SHALL BE CLASSIFIED |
| | ACCORDING TO SECTION 302.3.2. WITH NOT HAVING THE |
| | WAREHOUSE OCCUPANCY KNOWN WE MAY HAVE ADDITIONAL |
| | COMMENTS AND OR RATINGS PERTAINING TO THE OCCUPANCNCY |
| | UES. 106.1.2 ADDITIONAL INFORMATION REQUIRED. PLANS DO |
| | NOT INDICATE THE STORAGE OF ANY FLAMMABLE LIQUIDS |
| | (GASOLINE)? |
| | |
| | 3) THE SECOND FLOOR BEING A WAREHOUSE AND LIVE LOAD OF |
| | 125 LBS- SQ FT LOADING: |
| | 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. IT |
| | SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, |
| | PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F |
| | OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR |
| | LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT |
| | ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD |
| | CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY |
| | AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE |
| | SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER |
| | SQ FT.THE |
| | COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT |
| | RECORD OF THE BLDG DEPT. |
| | |
| | 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART OF |
| | A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS |
| | PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE |
| | BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON |
| | PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED & |
| | SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A |
| | CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE. |
| | SUCH PLATES SHALL NOT BE REMOVEDOR DEFACED, & IF |
| | LOST, REMOVED THE OWNER OF THE BUILDING SHALL REPLACE |
| | THEM. |
| | |
| | 4) EXISTING BUILDING CODE 906.1 THE MINIMUM |
| | REQUIREMENTS. ADDITIONS TO EXISTING BUILDING OR |
| | STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF |
| | CHAPTER 13 OF THE FLORIDA BUILDING CODE BUILDING. |
| | SUBMITTEDARE MANUAL J OR RESIDENTIAL HVAC FOR |
| | COMMERCIAL PLEASE USE MANUAL N. ADDITIONAL COMMENTS MAY |
| | APPEAR WITH THE CORRECT VERSION OF ENERGY CALCS. |
| | |
| | 5)THE FIRST FLOOR IS A ENCLOSED PARKING GARAGE AND |
| | WILL NEED TO MEET THE REQUIREMENTS OF 406.4 |
| | FBC-MECHANICAL FOR VENTILATION. |
| | |
| | 6)NEITHER SHEET 3 NOR 3A INDICATES THE USAGE OF THE |
| | ROOM. 106.1.2. ADDITIONAL INFO. PLANS WILL NEED TO SHOW |
| | THE HOW MANY SQ FT ARE GOING TO BE OFFICE AND LAYOUT OF |
| | OFFICE, THIS MAY ENACT |
| | ACCESSIBILITY ISSUES. |
| | |
| | 7) SHEET A4 & A5 BOTH INDICATE ROOF PLANS BUT NEITHER |
| | PLANS INDICATES ROOF DRAINAGE, THE NEW UPPER ROOF RUNS |
| | OFF ON TO THE LOWER ROOF BUT THE PLANS DO NOT PROVIDE |
| | HOW THE WATER WILL BE REMOVED FROM THE LOWER ROOF AREA? |
| | ROOF DRAINS WITH SECONDARY OVER FLOWS OR THROUGH THE |
| | WALL SCUPPERS? 1504.3. |
| | |
| | 8) PLEASE PROVIDE INFORMATION ON THE R-VALUE OF |
| | INSULATION TO BE PLACED AT THE ROOF? DETAIL A OF SHEET |
| | 5 INDICATES A WOD FRAME WALL INSULATED BUT THE AREA |
| | ABOVE THE CEILING AND BELOW THE INSULATION AT THE ROOF |
| | LEVEL IS MISSING INSULATION. PLEASE PROVIDE INSULATION |
| | IN THIS AREA, IT APPEARS TO BE PART OF THE A/C |
| | SPACE.13-402.1.A |
| | |
| | 9) . SHEET A5 CUT SECTIONS DIDN'T INDICATE FLOOR |
| | INSULATION ON THE AIR CONDITIONED SECOND FLOOR, THIS |
| | WILL NEED TO MEET EITHER 13-405.1.AB.1 WHERE THERE ARE |
| | TRADE OFFS UNDER THE ENERGY CODE COMPLIANCE FORMS, |
| | PLEASE UPDATE THE ENERGY FORMS WITH THECOMMERCIAL |
| | FORM. |
| | |
| | 10)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) ROOFING ASSEMBLIES |
| | B) TRUSS ANCHORS AND OR STRAPS |
| | |
| | 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 12)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | |
| | 13) CLOTH OR CANVAS AWNINGS: A LETTER FROM THE OWNER |
| | (NOT TENANT) IS TO ACCOMPANY ALLFABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO ACKNOWLEDGE |
| | THEIR RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED |
| | PRIOR TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF |
| | 75 MPH OR GREATER. THE LETTER MUST BE SIGNED BY THE |
| | OWNER NOT TENANT. |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH. |
| | |
| | 14) GUARDRAILS AT THE PARAPET PLEASE PROVIDE HOW |
| | ATTACHMENT TO THE EXISTING BUILDING WILL BE COMPLETED |
| | WITH COMPLIANCE TO: 1607.7.1.1 CONCENTRATED LOAD. |
| | HANDRAIL ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST |
| | A SINGLE CONCENTRATED LOAD OF 200 POUNDS (0.89 KN), |
| | APPLIED IN ANY DIRECTION AT ANY POINT ALONG THE TOP, |
| | AND HAVE ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO |
| | TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL |
| | ELEMENTS OF THE BUILDING. THIS LOAD NEED NOT BE ASSUMED |
| | TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN THE |
| | PRECEDING PARAGRAPH. |
| | |
| | 15) BUILDING PROVISO: |
| | 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION |
| | TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |