| Plan Review Notes For Permit 08040437 |
| Permit Number |
08040437 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-24 13:25:05 | ***DENIED*** | | | | | | 1) PLEASE MAKE CORRECTIONS TO CODE EDITIONS. WORK TO | | | COMPLY WITH NFPA 101, 2003, NFPA 72, 2002 AND NFPA 13, | | | 2002. SHT AN-1 | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. PLEASE ADD TO CODE REFERENCES. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 4) ACCESS CONTROL SYSTEM IS REFERENCED ON SHT AN-2 IN | | | HARDWARE NOTES. NO SUCH EQUIPMENT WAS FOUND ON PLANS OR | | | DOOR SCHEDULE. PLEASE CLARIFY AND IF SYSTEM IS PART OF | | | THE SCOPE OF THIS WORK, SEPARATE SHOP DRAWINGS AND | | | PERMIT ARE REQUIRED. ADDITIONALLY, WORK SHALL COMPLY | | | WITH NFPA 101, SECTION 7.2.1.6.2. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|