Plan Review Notes
Plan Review Notes For Permit 08040437
Permit Number 08040437
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-04-24 13:25:05***DENIED***
  
 1) PLEASE MAKE CORRECTIONS TO CODE EDITIONS. WORK TO
 COMPLY WITH NFPA 101, 2003, NFPA 72, 2002 AND NFPA 13,
 2002. SHT AN-1
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241. PLEASE ADD TO CODE REFERENCES.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 4) ACCESS CONTROL SYSTEM IS REFERENCED ON SHT AN-2 IN
 HARDWARE NOTES. NO SUCH EQUIPMENT WAS FOUND ON PLANS OR
 DOOR SCHEDULE. PLEASE CLARIFY AND IF SYSTEM IS PART OF
 THE SCOPE OF THIS WORK, SEPARATE SHOP DRAWINGS AND
 PERMIT ARE REQUIRED. ADDITIONALLY, WORK SHALL COMPLY
 WITH NFPA 101, SECTION 7.2.1.6.2.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756