| 2008-07-01 13:03:50 | |
| | |
| | |
| | |
| | ** DENIED2ND REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME |
| | NEW COMMENTS DUE TO CHANGES AND NEW INFORMATION ON |
| | PLANS NOT ON PREVIOUS PLANS. |
| | |
| | ** PLEASE BE SURE TO ADDRESS ALL COMMENTS AS SOME ARE |
| | REPEAT CODE SECTIONS. IF THERE ARE QUESTIONS ABOUT ANY |
| | OF THE NOTES BELOW PLEASE CALL TO GO OVER. |
| | |
| | *** AS STATED ON PREVIOUS REVIEW. THERE IS SOME ITEMS |
| | NOT YET SUBMITTED FOR REVIEW SO THOSE ITEMS CAN NOT YET |
| | BE REVIEWED FOR COMPLIANCE. |
| | |
| | |
| | 1) NOTE:THE PREVIOUS PLANS REFERENCED SOME NOTES FOR |
| | FIRE PUMP ALTHOUGH NOT IN PROJECT. THE PREVIOUS REVIEW |
| | NOTE #1 STATED TO PLACE THE 2003 NFPA-20 ON PLANS DUE |
| | TO FIRE PUMP REFERENCE. SINCE THERE IS NO FIRE PUMP, |
| | NFPA-20 DOES NOT NEED TO BE REFLECTED ON PLANS. IF THIS |
| | WERE THE ONLY COMMENT THIS WOULD BE REDLINED. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO |
| | REFERENCE OF LIFE SAFETY AND EMERGENCY SYSTEMS. |
| | RESPONSE MENTIONS ALL REFERENCE TO THESE SYSTEMS WILL |
| | BE REMOVED. PLEASE NOTE SYSTEMS AS OPTIONAL STAND-BY |
| | ONLY. PLANS ALONG WITH RISER STILL REFLECT L AND EQ . |
| | WHY ARE THERE TWO SEPARATE REFERENCES TO TYPE OF |
| | SYSTEMS? PLEASE INCLUDE ONLY THE DESIGNATIONS OF SOME |
| | SORT TO * OPTIONAL STAND-BY* ONLY. |
| | THE PREVIOUS REVIEW NOTE #2 ALSO REQUESTED TO SUBMIT |
| | THE MANUFACTURES SPECS/CUT SHEETS FOR THE ATS UNITS |
| | HOWEVER NO SPECS/SUBMITTALS OR DOCUMENTS WERE |
| | SUBMITTED. |
| | PLEASE SUBMIT. |
| | NEC 701,700, 702. 702.6, 110.3, 90.7 |
| | NFPA-110 |
| | FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION. |
| | |
| | |
| | 3) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | ARE NOT IN COMPLIANCE FOR THE MINIMUM REQUIRED BY FBC |
| | CHAPTER 13. |
| | PLEASE SEE SECTIONS 13-415.2.ABC.1.1, .1.2, .1.3, |
| | 13-415.2. |
| | PLEASE SEE SOME EXAMPLES WILL BE NOTED BELOW. THE INPUT |
| | DATA REPORT WILL BE NOTED AS IDR. |
| | ** IT IS IMPORTANT TO KNOW THAT THESE ARE *SOME* |
| | EXAMPLES ONLY AND ARE *NOT* AND EXHAUSTED LIST OF ALL |
| | ITEMS WHICH MAY NOT BE LISTED OR COMPLIANT. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE IDR FOR EXTERIOR LIGHTS. THE LIGHTING |
| | SHOWN ON THE IDR DOES NOT COORDINATE WITH PLANS. ONE OF |
| | THESE ITEMS IS ALL THE SITE LIGHTING. NONE OF THE SITE |
| | LIGHTING IS SHOWN ON THE IDR. WHERE ARE ALL OF THE 250W |
| | FIXTURES? WHERE ARE THE 175W FIXTURES? |
| | PLEASE TAKE A LOOK AT THE *Q* FIXTURES. |
| | ** MAKE NOTE THERE WILL BE COMMENTS BELOW WITH RESPECT |
| | TO EXTERIOR LIGHTING WHICH MAY CHANGE ON PLANS. |
| | |
| | FOR EXAMPLE: |
| | PLEASE ROOM AREA #110, 202, 234, 244, 243 ETC AS THERE |
| | ARE FIXTURES SHOWN ON PLANS WHICH ARE NOT LISTED ON THE |
| | FIXTURE LEGEND. HOW CAN THESE BE VERIFIED IF THE |
| | FIXTURES ARE NOT LISTED ON THE FIXTURE LEGEND? |
| | ** FIXTURES *AA*? |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE *DD* FIXTURES ON THE IDR AND PLANS. PLEASE |
| | SEE FIXTURE LEGEND WHICH INDICATES THESE AS 30WATTS YET |
| | THE IDR SHOWS A DIFFERENT VALUE FOR THE SAME FIXTURE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE HE FIXTURE IS MISSING FROM THE FIXTURE |
| | LEGEND. CAN NOT CONFIRM THE RATING ETC WITH THE IDR. |
| | THE FIXTURE CAN NOT BE *ASSUMED* TO BE THE SAME AS THE |
| | *H* AS THE *H* IS NOTED A PENDANT AND THE SYMBOL FOR |
| | THIS SAME FIXTURE IS TYPICAL FOR A |
| | RECESSED/CEILING/WALL MOUNTED FLUORESCENT TYPE |
| | FIXTURE. |
| | |
| | FOR EXAMPLE: |
| | THE IDR FOR WATER HEATERS ONLY SHOW ONE WATER HEATER AT |
| | 9KW. HOW IS THIS POSSIBLE WHEN THE PLANS SHOW AT LEAST |
| | 3 WATER HEATING SYSTEMS WHICH ARE ALL ELECTRICAL? ** |
| | PLEASE BE SURE TO ADJUST OTHER SYSTEMS SUCH AS PIPING |
| | ETC TO COORDINATE. |
| | |
| | ** THESE ARE SOME EXAMPLES GIVEN AS A BENEFIT. |
| | |
| | 4) NOTE: PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW FOR |
| | LIGHTING CONTROLS ARE STILL IN NEED OF ADDRESSING ALONG |
| | WITH NEW COMMENT DUE TO REVISED ITEM ON PLANS. PLEASE |
| | SEE SECTIONS 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE NEW OS SENSOR NOTED ON THE SYMBOL LEGEND |
| | INDICATES UNIT WITH *DAYLIGHT COMPENSATION* YET THE |
| | LIGHTING CONTROLS SHOWN ON THE IDR INDICATES *OCCUPANCY |
| | SENSOR WITHOUT DAYLIGHT SAVING*. |
| | PLEASE COORDINATE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE PREVIOUS NOTE WITH RESPECT TO CONTROL OF |
| | ALL EXTERIOR FIXTURES. A COUPLE OF THE *Q* FIXTURES ON |
| | PLANS ARE NOTED WITH A PHOTO-CELL NEXT TO THE FIXTURE |
| | HOWEVER NOT ALL. |
| | PLEASE SEE 13-415.1.ABC.1.4 FOR THE TWO PERMITTED |
| | METHODS. ONE OR THE OTHER IS REQUIRED. |
| | |
| | FOR EXAMPLE: |
| | THE RESPONSE MENTIONS TO SEE 7.03 AND 7.04 FOR EXTERIOR |
| | LIGHTING CONTROL AS THE SITE LIGHTING IS NOTED TO COME |
| | FROM THE LIGHTING CONTROL PANEL. |
| | HOW ARE THESE FIXTURES ON THE SAME LIGHTING CONTROL |
| | PANEL WHICH CONTROLS INTERIOR LIGHTS AS SHOWN? |
| | HOW ARE THESE SEPARATED? |
| | HOW DOES THIS LIGHTING CONTROL PANEL COMPLY WITH ONE OF |
| | THE TWO REQUIRED METHODS OF EXTERIOR LIGHTS? ONE METHOD |
| | PERMITTED IS PHOTO-SENSOR TYPE OR ASTRONOMICAL TIME |
| | CLOCK. WHEN ON ANY TIMED SCHEDULING THEN A MINIMUM |
| | BATTERY BACK UP IS REQUIRED FOR THE MINIMUM TIMES AS |
| | STATED IN THE SECTION OF THE CODE ABOVE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE INDICATE HOW THE SCHEDULING AND ZONES TAKE |
| | PLACE. |
| | PLEASE SEE THE SECTION OF THE CODE ABOVE |
| | 13-415.1.ABC.1.1 AS THE SYSTEMS ON EACH FLOOR SHALL BE |
| | INDEPENDENT. IT IS NOT PERMITTED TO HAVE THE LIGHTING |
| | CONTROL PANEL ON THE FIRST FLOOR CONTROL THE LIGHTING |
| | ON THE SECOND FLOOR, OR REVERSE. |
| | |
| | ** THESE ARE SOME EXAMPLES** |
| | PLEASE BE SURE TO SEE THE FOLLOWING COMMENT TWO |
| | COMMENTS. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH |
| | RESPECT TO THE MINIMUM LIGHTING LEVELS TO BE SHOWN IN |
| | PHOTO-METRICS FOR LIFE SAFETY CODE. |
| | THE RESPONSE MENTIONS TO SEE NEW LEVELS SHOWN ON E3.01. |
| | PLEASE TAKE A LOOK AT PLANS AS THE PLANS SHOW TWO |
| | TYPICAL STAIRS UNDER NORMAL ONLY. |
| | HOW CAN THE STAIRS BE TYPICAL WHEN THE LAYOUTS ARE NOT |
| | THE SAME? |
| | HOW CAN THE STAIRS BE TYPICAL LIGHTING LEVELS WHEN THE |
| | SAME LIGHT FIXTURES ARE NOT USED IN ALL STAIRS? AN |
| | EXAMPLE OF THIS IS *ME* FIXTURES AND *CE* FIXTURES. |
| | PLEASE VERIFY THESE FIXTURES UNDER EMERGENCY LEVELS. |
| | WILL THE BACK UP BALLAST PROVIDE THE 100 PERCENT RATING |
| | OF THE LUMEN OUTPUT AS THE NORMAL LEVEL? |
| | THIS WAS THE REASON FOR SHOWING THE LEVELS UNDER NORMAL |
| | AND EMERGENCY AND FOR EACH DIFFERENT STAIRWAY. PLEASE |
| | SEE NFPA-101 2003 7.8.1.3, 7.9.2.1, 7.9.2.2 FAC |
| | 61G15-33.004 |
| | |
| | 6) NOTE: THE PLANS NOW INDICATE NEW OCCUPANCY SENSORS |
| | FOR SOME OF THE EGRESS LIGHTS IN THE STAIRS. THIS IS |
| | PERMITTED BY BOTH THE LIFE SAFETY CODE AS WELL AS THE |
| | FLORIDA BUILDING CODE HOWEVER BOTH CODES REQUIRE THESE |
| | TYPES OF DEVICES TO *FAIL SAFE ON*. |
| | PLEASE ADJUST THE UNITS FOR STAIRS AND INCLUDE ON |
| | PLANS/SYMBOL LEGEND FOR FAIL SAFE ON DEVICES. NFPA-101 |
| | 2003 7.8.1.2.2, FBC 1006.2 |
| | |
| | 7) NOTE: PLEASE BE SURE TO ADJUST PANEL SCHEDULES AS |
| | CIRCUITS SHALL BE SPECIFIC TO ROOMS AND AREAS IN WHICH |
| | THEY FEED. PLEASE SEE PANEL *1L1* WHICH INDICATES |
| | DOZENS OF CIRCUITS TO *RECEPTACLES*. THESE WOULD |
| | INDICATE THE ROOM OR NUMERICAL DESIGNATION ON PLANS. |
| | NEC 408.4, 310.16, 240.4,220.44 ETC |
| | FBC 106.1.1, 106.5 FOR CLARITY, ADDITIONAL INFORMATION |
| | AND RECORD PLANS. |
| | |
| | 8) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE ANY |
| | EXTERIOR LIGHTS ON ANY OF THE THREE DOORS ON THE |
| | NORTH/NORTHEAST SIDE OF THE BUILDING. |
| | PLEASE KNOW ANY REVISIONS WOULD BE COORDINATED WITH |
| | OTHER SYSTEMS SUCH AS LOADS, CONTROLS, FIXTURE COUNTS |
| | ETC. |
| | ** NOTED ONLY** NO RESPONSE NEEDED. |
| | |
| | 9) NOTE: PLEASE SEE MISSING EXIT SIGN ON FIRST FLOOR |
| | FOR EGRESS INTO STAIR #4. |
| | LS-1017.10.1.1 |
| | |
| | 10) NOTE: PLEASE PROVIDE INFORMATION ON THE ACCESS |
| | CONTROL SNOW CLEARLY INDICATED ON PLANS. PLEASE SEE |
| | NFPA-101 2003 7.2.1.5, 7.2.1.5.1, 7.2.1.5.2 AS ALL |
| | DEVICES SHALL NOT IMPEDE MEANS OF EGRESS IN ANY |
| | CONDITION UNDER NORMAL OR UNDER EMERGENCY CONDITIONS. |
| | THIS INFORMATION IS REQUIRED ON BASE DESIGN EVEN AS THE |
| | ACCESS CONTROL SYSTEM WILL BE UNDER SEPARATE PERMIT AND |
| | PLANS. |
| | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, |
| | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS SIDE. |
| | |
| | 11) NOTE: PLEASE SEE 645.10 AS THE MEANS OF SHUTTING |
| | OFF THE MECHANICAL SYSTEM SHALL BE SIMILAR TO THE SAME |
| | SHUT OFF REQUIRED FOR OTHER ELECTRICAL EQUIPMENT. THE |
| | PUSHBUTTON FOR *OFF* WAS NOTED FOR THE PANEL HOWEVER |
| | THE A/C SYSTEM IN THIS SPACE DOES NOT INDICATE THE SAME |
| | TYPE OF SHUT OFF AT THE EGRESS DOOR. |
| | PLEASE ADD AND ADJUST ALL PLANS ACCORDINGLY. |
| | |
| | 12) NOTE: THE PREVIOUS REVIEW NOTED FBC 3006.2 WITH |
| | RESPECT TO THE ELEVATOR EQUIPMENT ROOM AND VENTILATION |
| | REQUIREMENTS. THE RESPONSE MENTIONS NEW EF-3 WAS ADDED |
| | YET NO CIRCUITING WAS LOCATED ON PLANS FOR UNIT, |
| | DISCONNECT ETC |
| | EF-#1 AND #2 ARE NOTED ON PANEL SCHEDULE HOWEVER NOT |
| | NEW #3. |
| | PLEASE ADJUST. |
| | 240.4, 220, 422, 310.16, ETC |
| | FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 13) NOTE: PLEASE SEE SITE LIGHTING PLANS ALONG WITH THE |
| | ELECTRICAL RISER DIAGRAM INDICATES AN *EQUIPMENT |
| | GROUNDING CONDUCTOR* AHEAD OF THE FIRST MEANS OF |
| | DISCONNECT. THIS IS NOT PERMITTED.THE GROUNDED |
| | CONDUCTOR IS BONDED AT THE FIRST MEANS OF DISCONNECT |
| | PER CODE.WHEN THIS TAKES PLACE IF AN EQUIPMENT |
| | GROUNDING CONDUCTOR WAS INSTALLED BEFORE THIS FIRST |
| | MEANS OF DISCONNECT THIS WOULD CREATE OBJECTIONABLE |
| | CURRENTS BETWEEN THE NEUTRAL AND THE EQUIPMENT GROUND. |
| | PLEASE SEE 250.24, 250.6 AS ADJUST RISER AND PLANS. |
| | |
| | 14) NOTE: PLEASE SEE 240.13 AND 230.95. THE GFP WAS |
| | ADDED AND NOW SHOWN ON THE MAIN DIST BOARD INSIDE THE |
| | BUILDING. PLEASE SEE THE SECTIONS OF THE CODE AS THIS |
| | IS REQUIRED AT THE MAIN. THE NEW MAIN OUTSIDE IS A NEW |
| | FUSED DISCONNECT. HOW WILL THE GFP BE PROVIDED ON A |
| | FUSED SAFETY SWITCH? |
| | PLEASE VERIFY THE MAIN DIST BOARD INSIDE STILL |
| | CONTAINING A MAIN. |
| | PLEASE ADJUST AND REVISE PLANS ACCORDINGLY. |
| | |
| | 15) NOTE: PLEASE SEE RISER AS THE *1TL* TRANSFORMER IS |
| | SHOWING 1/0 CONDUCTORS ON THE SECONDARY SIDE WHICH |
| | TERMINATES INTO A 200AMP MAIN CIRCUIT BREAKER AT PANEL |
| | *1LL*. THE 1/0 CONDUCTORS ARE NOT RATED. |
| | 240.21, 240.4, 310.16. AN EXAMPLE OF THIS WAS GIVEN ON |
| | PREVIOUS REVIEW FOR CONDUCTORS FORM *1TN* THOSE WERE |
| | CORRECTED. |
| | |
| | 16) NOTE: PLEASE SEE THE CONDUCTORS FROM THE MDP TO |
| | TRANSFORMER *1TN*. THESE ARE NOTED ON THE RISER WITH A |
| | #10 FOR THE FEEDER LEGEND WHICH SHOWS 1/0 ONCE AGAIN ON |
| | A 200AMP BREAKER. |
| | PLEASE SEE 240.4, 310.16, 110.14 AS 1/0 IS NOT RATED |
| | FOR THE 200AMPS. |
| | |
| | 17) NOTE: PLEASE BE SURE TO SEE THE SCHEDULE FOR MDP AS |
| | THIS SHOWS 150AMP BREAKER/OVER CURRENT PROTECTION FOR |
| | THE SAME *1TN*. PLEASE COORDINATE. |
| | PLEASE SEE 450.3 AS THE MAXIMUM OVER CURRENT PROTECTION |
| | FOR THIS SIZE TRANSFORMER IS NOT PERMITTED TO BE OVER |
| | 125%. |
| | 240.4, 310.16, 450.3 ETC |
| | PLEASE ADJUST AND COORDINATE ALL. |
| | FBC 106.1.1, 106.1.2 |
| | |
| | 18) NOTE: THE RISER NOTES AND SHOWS THE DISCONNECT AND |
| | GFI RECEPTACLE FOR CHILLER HOWEVER PLEASE LOCATE ON THE |
| | PLANS THE ACTUAL LOCATION OF THESE ITEMS. |
| | 210.63, 440.11. |
| | |
| | 19) NOTE: PLEASE PLACE NOTE ON PLANS FOR *ALL DEVICES* |
| | TO MEET 11-4.27. THE RESPONSE MENTIONS THE FIRE ALARM |
| | DEVICES NOW INDICATE HEIGHTS. HOWEVER THE SECTION OF |
| | CODE REFLECTED ON PREVIOUS REVIEW WAS NOT FOR FIRE |
| | ALARM DEVICES. |
| | THE CODE SECTION IS GIVEN BELOW: |
| | ** |
| | 11-4.27 CONTROLS AND OPERATING MECHANISMS. 11-4.27.1 |
| | GENERAL. |
| | CONTROLS AND OPERATING MECHANISMS REQUIRED TO BE |
| | ACCESSIBLE BY SECTION 11-4.1 SHALL COMPLY WITH SECTION |
| | 11-4.27. |
| | 11-4.27.2 CLEAR FLOOR SPACE. |
| | CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2.4 THAT |
| | ALLOWS A FORWARD OR A PARALLEL APPROACH BY A PERSON |
| | USING A WHEELCHAIR SHALL BE PROVIDED AT CONTROLS, |
| | DISPENSERS, RECEPTACLES AND OTHER OPERABLE EQUIPMENT. |
| | 11-4.27.3 HEIGHT. |
| | THE HIGHEST OPERABLE PART OF CONTROLS, DISPENSERS, |
| | RECEPTACLES, AND OTHER OPERABLE EQUIPMENT SHALL BE |
| | PLACED WITHIN AT LEAST ONE OF THE REACH RANGES |
| | SPECIFIED IN SECTIONS 11-4.2.5 AND 11-4.2.6. ELECTRICAL |
| | AND COMMUNICATIONS SYSTEM RECEPTACLES ON WALLS SHALL BE |
| | MOUNTED NO LESS THAN 15 INCHES (380 MM) ABOVE THE |
| | FLOOR. |
| | EXCEPTION: THESE REQUIREMENTS DO NOT APPLY WHERE THE |
| | USE OF SPECIAL EQUIPMENT DICTATES OTHERWISE OR WHERE |
| | ELECTRICAL AND COMMUNICATIONS SYSTEMS RECEPTACLES ARE |
| | NOT NORMALLY INTENDED FOR USE BY BUILDING OCCUPANTS. |
| | 11-4.27.4 OPERATION. |
| | CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE |
| | WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 LBF |
| | (22.2 N). |
| | ** THIS WAS EXTRACTED FROM THE FBC FOR INFORMATION. |
| | THIS MAY AFFECT OPERATING DEVICES IN AREAS FOR ADA SUCH |
| | AS BREAK ROOMS ETC. |
| | |
| | 20) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME AS SOME OF THE SAME CODE |
| | SECTIONS GIVEN IN PREVIOUS REVIEW ARE REPEATED. PLEASE |
| | KNOW AT THIS TIME SOME PLANS ARE BEING RETAINED ALONG |
| | WITH ONE SET OF CALCULATIONS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |