| Plan Review Notes For Permit 08040391 |
| Permit Number |
08040391 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-10-25 15:47:02 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING DEFICIENCIES REMAIN AND SHALL BE | | | ADDRESSED PRIOR TO PERMIT ISSUANCE: | | | | | | 1. ADDRESS BUILDING PLAN REVIEW COMMENTS RELATED TO | | | WIND LOAD ANALYSIS FOR OARTU-1. | | | | | | 2. NO LETTER WAS INCLUDED WITH THIS SUBMISSION FROM | | | TRANE REGARDING THEIR ACCEPTANCE OF THE PROPOSED | | | REDUCED CLEARANCES FOR SERVICE AND REPLACEMENT OF | | | COOLING COILS. ONCE SAID LETTER (TWO COPIES) IS | | | PROVIDED, A PROVISO WILL BE ISSUED REQUIRING FIELD | | | VERIFICATION BY MECHANICAL INSPECTOR THAT SUFFICIENT | | | SPACE EXISTS FOR PROPER SERVICE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|