| 2008-10-28 08:13:06 | |
| | ** DENIED 2ND REVIEW** |
| | |
| | |
| | 1) NOTE: NEW NOTE WHICH WAS NOT PART OF THE PREVIOUS |
| | REVIEW. |
| | PLEASE SEE NEC 700.9B THE AHU MAY NOT BE FED FROM THE |
| | LIFE SAFETY PANEL OR EQUIPMENT. PLEASE KNOW THIS LOAD |
| | IS NOT A LIFE SAFETY OR LEGALLY REQUIRED LOAD. PLEASE |
| | ADJUST RISER TO INCLUDE EQUIPMENT TO CREATE AN |
| | *OPTIONAL STAND-BY* SYSTEM WHICH STILL MAY BE FED FROM |
| | THE SAME GENERATOR IF THE LOAD AND SIZE OF GENERATOR |
| | PERMITS WITHOUT LOAD SHEDDING. |
| | THIS COMMENT WILL SUBSTANTIALLY CHANGE THE CIRCUITING, |
| | RISER ETC. |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |