| Date |
Text |
| 2008-04-18 16:38:20 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | NOTE: SHEET M0.2, M.2.3, AND P2.1 ARE INDICATING 1" |
| | NATURAL GAS TO THE OARTU-1 CHILLED WATER UNIT. |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS |
| | SECTION 401.1 SCOPE. |
| | |
| | 3. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL) |
| | ON THE GAS ISOMETRIC. PER FBC FUEL GAS SECTION 401.1 |
| | SCOPE. |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | *NOTE: THIS INCLUDES THE EXISTING NATURAL GAS SYSTEM |
| | IN THE KITCHEN THAT THE NEW PROPOSED OARTU-1 UNIT IS |
| | CONNECTING TO. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | *NOTE: THIS INCLUDES THE EXISTING NATURAL GAS SYSTEM |
| | IN THE KITCHEN THAT THE NEW PROPOSED OARTU-1 UNIT IS |
| | CONNECTING TO. |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | NOTE: IF NATURAL GAS DELIVERY PRESSURE IS 2 PSI OR |
| | MORE PLEASE PROVIDE TWO COPIES OF THE MP REGULATOR |
| | MANUFACTURER'S SPECIFICATIONS THAT CLEARLY INDICATE THE |
| | MAKE MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING |
| | FROM A NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | *NOTE: PROVIDE TWO COPIES OF MANUFACTURER'S |
| | SPECIFICATION SHEETS OF THE NEW CHILLED WATER OARTU-1 |
| | UNIT THAT CLEARLY INDICATE THE MAKE, MODEL NUMBER, BTU |
| | CAPCITY, AND A LISTING FROM A NATIONALLY RECOGNIZED |
| | TESTING LABORATORY. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |