| 2008-04-16 14:29:32 | RESIDENTIAL(R2)SHUTTERS INSTALLATION, BUILDING |
| | REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1-AS PER SEC. 1609.4(3)THIS PROPERTY IS CONSIDERED |
| | TO BE IN EXPOSURE "C". THEREFORE, OPENINGS DESIGN |
| | PRESSURES NEED TO BE REVISED ACCORDING TO TABLE |
| | 1609.6.2.1(2) AND TABLE 1609.6.2.1(4) OF FBC 2004. |
| | REVISE OPENING DESIGN PRESSURES AS REQUIRED.ALSO, |
| | CLEARLY SPECIFYIN THE KEY PLAN THE LOCATION OF |
| | OPENINGS TOVERIFY IFOPENINGSARE LOCATED ON |
| | INTERIOR OR END ZONE AS REQUIRED BY FIGURE 1609.6.2.2 |
| | FBC 2004. THISWILL MAKE A DIFFERENCE ON THE DESIGN |
| | PRESSURES. |
| | |
| | 2- SHUTTER INSTALLATION SCHEDULE SPECIFIES ANCHORS TO |
| | BE1/4 - 1 1/4 ELCOL BUILDEX HEX HEAD MAXI SET TAPCON. |
| | SEE GENERAL NOTES ON SHEET 1 OF 9 OF STORM SHUTTERS FOR |
| | MINIMUM ANCHOR EMBEDMENT REQUIRED AND REVISE SIZE OF |
| | TAPCON AS REQUIRED. |
| | |
| | 3- SHUTTER MOUNTING CONDITION ON COLUMN #4OF |
| | INSTALLATION SCHEDULESPECIFIES SECT. 2 FOR ALL |
| | OPENINGS. THERE ARE SOME OTHER MOUNTING CONDITIONS |
| | HIGHLIGHTED ON SHEET 3 OF 9 AND 6 OF 9.REVISE AS |
| | REQUIRED TO IDENTIFY EACH OPENING WITH EACH TYPE OF |
| | MOUNTING CONDITION. |
| | |
| | 4-SHUTTER SPANSIZE SPECIFIED ON INSTALLATION |
| | SCHEDULE COLUMN #6IS ONLY 3" LONGER THAN THE OPENING |
| | SIZE SHOWN ON COLUMN #2.CLARIFY HOW ARE YOU GOING TO |
| | OBTAIN THE 3.5" MINIMUM EDGE DISTANCESHOWN ON COLUMN |
| | #8. |
| | NOTE:REMEMBER THAT EDGE DISTANCE APPLIES TO TOP AND |
| | BOTTOM INSTALLATIONS. REVISE AS REQUIRED. |
| | |
| | 5- SPECIFY WHAT ARETHEABBREVIATIONS PC/CB SHOWN ON |
| | COLUMN #11 STANDING FOR. |
| | NOTE:KEEP IN MIND THAT IF SUBSTRATE IS CONCRETE |
| | BLOCK, THEN CONCRETE BLOCK ANCHOR TYPE AND SPACING |
| | TABLE SHALL BE USED.ALSO,CONCRETE FILLED CONCRETE |
| | BLOCK CELLS DON'T QUALIFY AS CONCRETE BLOCK SUBSTRATE |
| | UNLESSPROOF/TESTING IS PROVIDED SHOWING ACTUAL |
| | CONSTRUCTION. |
| | |