| 2008-04-22 16:32:58 | 2004 FBC W/2007 REVISIONS |
| | CHANGE OF OCCUPANCY |
| | ENCLOSE PORTION OF GARAGE FOR OFFICE |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED |
| | BY FBC 13-600. THE OWNER/AGENT IS REQUIRED TO SIGN THE |
| | FORMS. |
| | |
| | 3) PROVIDE A WALL SECTION OF THE NEW INTERIOR WALLS |
| | INDICATING THE FRAMING MATERIALS, STUD SPACING, |
| | INSULATION, DRYWALL THICKNESS, ETC. |
| | |
| | 4) THE WALL ADJACENT TO THE STORAGE AREA IS REQUIRED TO |
| | BE INSULATED. SPECIFY THE R-VALUE OF THE INSULATION IN |
| | THE ATTIC, EXTERIOR, COMMON AND ADJACENT WALLS. THE |
| | DOOR IN THE ADJACENT WALL IS REQUIRED TO COMPLY WITH |
| | FBC 13-603 AND CAN NOT BE HOLLOW CORE. SEE FBC 13-600. |
| | |
| | 5) SPECIFY ON THE PLANS WHICH WALLS ARE NEW AND WHICH |
| | ARE EXISTING. |
| | |
| | 6) THE PROPOSED OFFICE IS REQUIRED TO COMPLY WITH FAIR |
| | HOUSING REQUIREMENT 4 FOR ACCESSIBLE ROUTE AND |
| | REQUIREMENT 3 FOR USABLE DOORS. USABLE DOORS ARE |
| | REQUIRED TOHAVE A NOMINAL 32" CLEAR OPENING MEASURED |
| | FROM THE STOP TO THE FACE OF THE DOOR WHEN OPEN 90 |
| | DEGREES. THE FLOOR OF THE OFFICE IS REQUIRED TO BE |
| | LEVEL WITH THE EXISTING HABITABLE SPACE. SHOW |
| | COMPLIANCE WITH THESE REQUIREMENTS. SHOW THE LOCATIONS |
| | OF ANY FLOOR ELEVATION CHANGES ON THE PLANS. THE LIGHT |
| | SWITCHES, RECEPTACLES AND CONTROLS ARE REQUIRED TO |
| | COMPLY WITH REQUIREMENT 5. SEE FBC CHAPTER 11 PART B |
| | FAIR HOUSING. |
| | |
| | 7) TEST RTW |
| | |