| 2008-04-21 11:46:22 | 08040322 |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1. SOME OF THE PAGES ARE NOT NUMBERED; THEREFORE, IT IS |
| | DIFFICULT TO CLEARLY IDENTIFY PLAN REVIEW ISSUES.THIS |
| | DELAYS THE NEXT PLAN REVIEW. |
| | |
| | 2. THE SECTION TITLED NOTES, GOVERNING CODE SHOULD |
| | INCLUDE 2007 REVISIONS/SUPPLEMENTS. |
| | |
| | 3. NOTE REFERS TO WINDOW AND DOOR PRODUCT APPROVAL |
| | NUMBERS INCLUDING REVISION NUMBER AND ARE NOT |
| | CONSISTENT.PLEASE REVISE. |
| | |
| | 4. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72.THE EVALUATION REPORT AND INSTALLATION |
| | INSTRUCTIONS ARE REQUIRED IN ADDITION TO THE COVER |
| | SHEET (WHICH WAS PROVIDED). |
| | |
| | 5. SOMEONE WROTE ENTIRE SUNROOM IS IMPACT PROTECTED ON |
| | THE PLAN.IT APPEARS THAT THE GLAZING IS NON IMPACT. |
| | PLEASE CLARIFY THIS STATEMENT.ONLY THE PERSON WHO HAS |
| | SEALED THE DOCUMENT CAN ALTER IT, AND SHOULD DO SO BY |
| | CLOUDING THAT CHANGE, AND ALSO INITIAL AND DATE. |
| | HOWEVER, IT IS PREFERABLE THAT THE DESIGNER INCORPORATE |
| | CHANGES INTO THE PLAN. |
| | |
| | 6.REMOVE REFERENCES TO ROOF PANELS FROM THE PLAN. |
| | SOME HAVE BEEN CROSSED OUT WITH BLACK MARKER.THE |
| | APPLICATION STATES THAT THE ROOF IS EXISTING.PLEASE |
| | MAKE PLANS CONSISTENT WITH |
| | |
| | 10. PROVIDE A PARTIAL FLOOR PLAN SHOWING ROOM |
| | DESIGNATIONS.SHOW ALL ROOMS WHICH HAVE OPENINGS, |
| | DOORS OR WINDOWS, WHICH OPEN INTO THIS NEW ROOM.IF |
| | ANY OF THESE ROOMS ARE BEDROOMS, SHOW HOW EMERGENCY |
| | EGRESS IS AFFECTED FBC301. |
| | |
| | 11. ENGINEERING WAS PROVIDED IN THE PLAN FOR MULLIONS. |
| | PRODUCT APPROVAL IS REQUIRED FOR THE MULLIONS, |
| | FAC9B72. |
| | |
| | 12. SHOW IMPACT PROTECTION FOR THE WALL SEPARATING THE |
| | BUILDING INTERIOR FROM THIS SPACE, FBC R301.2.1.2(1). |
| | |
| | |