| Plan Review Notes For Permit 08040313 |
| Permit Number |
08040313 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-09-25 08:05:34 | | | | | | | PROVISO | | | | | | THE CONDENSING UNIT MUST BE A MINIMUM OF 3' FROM THE | | | SERVICE. 110.26 NEC | | | | | | A RECEPTACLE PER 210.63 IS REQUIRED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|