| 2008-04-17 13:23:29 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET M/P-1 SANITARY RISER PLEASE CORRECT THE |
| | FOLLOWING ITEMS. |
| | |
| | A} THE WASHING MACHINE DOES NOT REFLECT THE FLOOR PLAN |
| | ON THE SANITARY RISER. THE SANITARY RISER IS INDICATING |
| | THE WASHER IN THE EXISTING SCREEN PORCH. PLEASE CORRECT |
| | THIS PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS AND FBC PLUMBING |
| | SECTION 701.1 SCOPE. |
| | |
| | B} THE WASHING MACHINE STACK REQUIRES A 3" CLEANOUT TO |
| | BE LOCATED AT 4' A.F.F. PER FBC PLUMBING SECTION 708.7 |
| | MINIMUM SIZE AND SECTION 708.9 ACCESS. |
| | |
| | C} THE LAVATORY REQUIRES A WATER SEAL TRAP. PER FBC |
| | PLUMBING SECTION 1002.1 FIXTURE TRAPS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |