Plan Review Notes
Plan Review Notes For Permit 08040310
Permit Number 08040310
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-14 18:30:45RESIDENTIAL (R2) WINDOW CHANGE OUT, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- ACCORDING TO SEC. 1609.4(3) FBC 2004 THE BUILDING IS
 LOCATED IN EXPOSURE "C". THEREFORE, WINDOWS NEED TO
 MEET THE DESIGN PRESSURES FOR EXPOSURE "C" AS PER
 TABLES 1609.6.2.1(2) AND TABLE 1609.6.2.1(4) FBC 2004.
 SPECIFY BUILDING MEAN ROOF HEIGHT AND IF WINDOWS ARE
 LOCATED ON END ZONE OR INTERIOR ZONE TO VERIFY
 COMPLIANCE WITH THE PRODUCT APPROVAL AND DESIGN
 PRESSURES.
  
 2- ACCORDING TO KEY PLAN SUBMITTED, WINDOWS ARE 51-
 3/4" X 52 -7/8".WINDOW SIZE SHOWN ONSHEET 2 OF FOUR
 ARE 53-1/8" X 63".THESE WINDOWS ARE BIGGER THAN THE
 OPENINGS WHERE WINDOWS WILL BE INSTALLED. CONTRACTOR IS
 NOT ALLOWED TO DO STRUCTURAL CHANGES IF HOLDING LICENSE
 U-19530 FOR DOOR AND WINDOW REPLACEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712