| Plan Review Notes For Permit 08040298 |
| Permit Number |
08040298 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-08-01 16:35:41 | PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND | | | STAMPED. HOWEVER, CORRECTIONS TO THE ENERGY CODE | | | COMPLIANCE FORM ARE REQUIRED BEFORE REVIEW STATUS WILL | | | BE PASSED: | | | | | | 1. THE ADDRESS LISTED ON THE COVER PAGE OF THE | | | COMPLIANCE FORM IS LISTED AS 1641 WORTHINGTON RD. THIS | | | IS NOT THE ADDRESS FOR THIS PROJECT. PLEASE CORRECT. | | | | | | 2. THE SYSTEM SIZING SUMMARY SHALL BE SIGNED AND SEALED | | | IN ADDITION TO THE ENERGY CALCULATIONS IN ACCORDANCE | | | WITH FBCB 13-407.1.ABC.1(2). | | | | | | IF THESE ITEMS CAN BE CORRECTED DURING THIS REVIEW | | | CYCLE, THE REVIEW STATUS WILL BE CHANGED TO PASS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|