| 2008-08-05 09:37:42 | BUILDING PLAN REVIEW |
| | PERMIT: 08040298 |
| | ADD: 406 COLUMBIA DRIVE |
| | CONT: WEST CONSTRUCTION |
| | TEL: (561)588-2027 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 2-5) COMPLIED. |
| | |
| | 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 6A) COMPLIED |
| | 6B) COMPLIED |
| | 6C) COMPLIED |
| | 6D) EXTERIOR LOUVERS/ VENT 3"X10" OK NOT TO NEED |
| | PRODUCT APPROVAL/ SIMILAR AS GLASS BLOCK WILL NOT |
| | PRESSURIZE WHOLE BUILDING IF DAMAGED. |
| | 6E) ROOFING ASSEMBLIES/ROOF TILE- INDICATE TYPE OF |
| | FASTENING SYSTEM |
| | |
| | 7)USING NOA'S OK COMPLIED |
| | |
| | 8)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9)PLEASE PROVIDE ENERGY COMPLIANCE FORMS FOR NEW |
| | CONSTRUCTION SEE 13.400.0 ABC . |
| | 9A) PLEASE PROVIDE THE CORRECT ADDRESS ON THE PROJECT |
| | SUMMARY SHEET. |
| | 9B) THE INPUT DATA REPORTSHEET 2& 3 FOR WALLS |
| | INDICATES THE USE OF 8 INCH BLOCK WITH 3/4" ISO |
| | INSULATION SWERE AS SHEET A-2 DETAILS 5 & 6 SHOW STUCCO |
| | DIRECTLY APPLIED TO THE INTERIOR WALLS. |
| | 9C) EXTERIOR DOORS 1 & 3 BOTH SHOW AS A INSULATED DOOR |
| | SYSTEM BUT THE PRODUCT APPROVALS SUBMITTED ARE NOT. |
| | 9D) ROOF INSULATION THE COMPLIANCE FORM INDICATES THE |
| | USE OF 6 INCH BATTS WHERE AS THE PLANS CALL FOR FOAN |
| | ISONENE INSULATION, PLEASE PROVIDE MANUFACTURERS |
| | INFORMATION AS TO THE THICKNESS AND R-VALUES |
| | FOR THIS TYPE INSULATION. |
| | 9E) IN THE INPUT DATA REPORT SHEET # 4 FOR FLOORS YOU |
| | HAVE TAKEN INSULATION VALUES FOR CARPET AND RUBBER PAD, |
| | PLEASE CORRELATE PLANS AND ENERGY CALCS. |
| | 9F) PLEASE SEE SHEET # 5 FOR FENESTRATION, THE INPUT |
| | REPORT IS BLANK FOR GLAZED OPENINGS WHERE ASSHEET A-2 |
| | DETAIL 4 INDICATES 27 SQ FT OF GLAZED OPENING, AGAIN |
| | PLEASE CORRELATE. |
| | |
| | 10)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |