| 2008-04-14 19:03:58 | ** DENIEDREVIEW** |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES NEED TO BE |
| | STATED ON PLANS. (ELECTRICAL SHEETS AT A MINIMUM). |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THAT NO ENERGY CALCULATIONS AS |
| | REQUIRED PER FBC CHAPTER 13 WERE SUBMITTED. |
| | PLEASE BE SURE TO SEE 13-400.3.A, 13-400.3.B, |
| | 13-400.3.C, 13-415.2.ABC.1.1, .1.2 AND .1.3, 13-415.2 |
| | ETC |
| | PLEASE SEE COMPLIANCE WITH THE FBC AND CHAPTER 13 CAN |
| | NOT BE VERIFIED AT THIS TIME. |
| | PLEASE ALSO SEE COMMENTS FROM MECHANICAL AND BUILDING |
| | REVIEWS. |
| | ** THE LIGHTING PERFORMANCE ADDED TO E4.1 DOES NOT MEET |
| | THE MINIMUM FOR CODE COMPLIANCE AT THIS TIME. |
| | |
| | 3) NOTE: PLEASE SEE THE FIXTURES WHICH ARE SHOWN ON |
| | E0.1 AND E4.1 DO NOT CORRELATE. |
| | PLEASE SEE NOTE #2 ABOVE AND BE SURE TO ADJUST ALL. |
| | |
| | 4) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE AS |
| | RISER SHOWS PANEL AS 100AMP MCB AND THE PANEL SHOWS |
| | 90AMP MLO WHICH CONTAINS NO MAIN AS REQUIRED. |
| | FBC 106.1.2 FOR COORDINATION AND NEC 230.70, 71, 76, 79 |
| | FOR MAIN. |
| | |
| | 5) NOTE: PLEASE SEE MISSING REQUIRED FOOTER STEEL PER |
| | 250.50 AND ANY METALLIC COLD WATER PIPE. |
| | THE GROUNDING DETAIL ON E7.1 IS NOT COMPLETE WITH THESE |
| | ITEMS. |
| | PLEASE ALSO SEE THE GROUNDING DETAIL MENTIONS TO SEE |
| | PANEL FOR THE SIZE OF THE GROUNDING ELECTRODE PER |
| | 250.66 YET THE RISER SHOWS A GROUNDING ELECTRODE |
| | CONDUCTOR OF A DIFFERENT SIZE?? |
| | PLEASE COORDINATE AND ADJUST PLANS. |
| | |
| | 6) NOTE: PLEASE SEE OCTAGONAL NOTES ON RISER WHICH ARE |
| | NOT ON THE KEYED NOTE SCHEDULE. |
| | FOR EXAMPLE: #4. |
| | |
| | 7) NOTE: INFORMATION HAS BEEN ROUTED TO THE ADDRESSING |
| | REVIEWER. ONCE THE FINAL ADDRESS HAS BEEN DETERMINED, |
| | PLEASE BE SURE TO ADD THE CORRECT ADDRESS TO THE TITLE |
| | BLOCKS ON EACH SHEET. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | FBC 106.3.5 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |