| Plan Review Notes For Permit 08040251 |
| Permit Number |
08040251 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-14 10:02:15 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS | | | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | 1} SHEET FP1 INDICATES AN OPTIONAL ELECTRICAL PLAN. IF | | | THIS IS THE CORRECT PLAN, INCLUDING A 100 AMP PANEL, | | | SUBMIT AN ELECTRICAL RISER DIAGRAM INDICATING | | | COMPLIANCE WITH 225.31 DISCONNECTING MEANS AND 250.32 | | | FOR GROUNDING ELECTRODE CONDUCTOR. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|