Notes
Date Text
2008-04-14 16:58:15 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E-1 LIGHTING PERFORMANCE CALCULATIONS INDICATE
 ALL THE LUMINAIRES TO BE 32 VA. THE LIGHTING SCHEDULE
 HAS DIFFERENT WATTAGES INDICATED FOR THE DIFFERENT
 FIXTURE TYPES. CORRELATE SAME TO INDICATE THE PROPOSED
 THE TYPES BEING INSTALLED. RECALCULATE THE DENSITIES.
  
 2} SHEET E-1 HAS TRACK LIGHTING, "C" TYPE FIXTURE IS
 NOT LISTED ON THE LIGHTING SCHEDULE. SEE 13-415.2
 ABC.1.2, 3 AND 4 REGARDING TRACK LIGHTING.
  
 3} SEE 13-415.1ABC.1.2 REGARDING SPACE CONTROLS AND
 INCLUDE LOCATIONS ON PLANS.
  
 4} CIRCUIT NUMBERS AND PANEL DESIGNATIONS ARE REQUIRED
 FOR THE LIGHTING CIRCUITS AND MUST CORRELATE WITH THE
 SCHEDULES.408.4 NEC AND 106.3.5.1.2 FBC AS AMENDED.
  
 5} REGARDING THE BATTERY PACK UNITS, CIRCUIT THEM PER
 700.12(F)(4) NEC.. INDICATE SAME ON THE PLAN.
  
 6} NOTE #5, SHEET E-1 REGARDING RESTROOM LIGHTS IS
 ATTACHED TO THE TRACK LIGHTING?
  
 7} SHEET E-3 RISER DIAGRAM ERRONEOUSLY INDICATES THE
 SERVICE IS A 5 PHASE 120/240 DELTA WITH A HIGH LEG ON
 "C" PHASE.IN VIOLATION OF 408.3(E). THE HIGH LEG IS
 MARKED ON "B" PHASE IN THE PANEL SCHEDULE, WITH SINGLE
 PHASE CIRCUITS ON THAT PHASE. THE DESIGNER SHOULD
 CONTACT FPL FOR THE CORRECT INFORMATION ON THE SERVICE
 AVAILABLE AT THE LOCATION OF THE PROJECT. ALTHOUGH
 HIGHLY UNLIKELY IT WOULD BE A 120/240 DELTA, IF
 CONFIRMED THE PANEL BRANCH CIRCUITS SHALL BE ARRANGED
 ACCORDINGLY.
  
 8} THE PANEL SCHEDULES ON E-3 DO NOT INDICATE
 COMPLIANCE WITH 210.8 (B) FOR GFCI PROTECTION, ALSO NO
 INDICATION ON SHEET E-2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER