| 2008-04-14 16:58:15 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} SHEET E-1 LIGHTING PERFORMANCE CALCULATIONS INDICATE |
| | ALL THE LUMINAIRES TO BE 32 VA. THE LIGHTING SCHEDULE |
| | HAS DIFFERENT WATTAGES INDICATED FOR THE DIFFERENT |
| | FIXTURE TYPES. CORRELATE SAME TO INDICATE THE PROPOSED |
| | THE TYPES BEING INSTALLED. RECALCULATE THE DENSITIES. |
| | |
| | 2} SHEET E-1 HAS TRACK LIGHTING, "C" TYPE FIXTURE IS |
| | NOT LISTED ON THE LIGHTING SCHEDULE. SEE 13-415.2 |
| | ABC.1.2, 3 AND 4 REGARDING TRACK LIGHTING. |
| | |
| | 3} SEE 13-415.1ABC.1.2 REGARDING SPACE CONTROLS AND |
| | INCLUDE LOCATIONS ON PLANS. |
| | |
| | 4} CIRCUIT NUMBERS AND PANEL DESIGNATIONS ARE REQUIRED |
| | FOR THE LIGHTING CIRCUITS AND MUST CORRELATE WITH THE |
| | SCHEDULES.408.4 NEC AND 106.3.5.1.2 FBC AS AMENDED. |
| | |
| | 5} REGARDING THE BATTERY PACK UNITS, CIRCUIT THEM PER |
| | 700.12(F)(4) NEC.. INDICATE SAME ON THE PLAN. |
| | |
| | 6} NOTE #5, SHEET E-1 REGARDING RESTROOM LIGHTS IS |
| | ATTACHED TO THE TRACK LIGHTING? |
| | |
| | 7} SHEET E-3 RISER DIAGRAM ERRONEOUSLY INDICATES THE |
| | SERVICE IS A 5 PHASE 120/240 DELTA WITH A HIGH LEG ON |
| | "C" PHASE.IN VIOLATION OF 408.3(E). THE HIGH LEG IS |
| | MARKED ON "B" PHASE IN THE PANEL SCHEDULE, WITH SINGLE |
| | PHASE CIRCUITS ON THAT PHASE. THE DESIGNER SHOULD |
| | CONTACT FPL FOR THE CORRECT INFORMATION ON THE SERVICE |
| | AVAILABLE AT THE LOCATION OF THE PROJECT. ALTHOUGH |
| | HIGHLY UNLIKELY IT WOULD BE A 120/240 DELTA, IF |
| | CONFIRMED THE PANEL BRANCH CIRCUITS SHALL BE ARRANGED |
| | ACCORDINGLY. |
| | |
| | 8} THE PANEL SCHEDULES ON E-3 DO NOT INDICATE |
| | COMPLIANCE WITH 210.8 (B) FOR GFCI PROTECTION, ALSO NO |
| | INDICATION ON SHEET E-2. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |