| Plan Review Notes For Permit 08040240 |
| Permit Number |
08040240 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-17 13:22:04 | ***DENIED*** | | | | | | 1) THE MANUFACTURER SPECIFICATION SHEETS IDENTIFY | | | ACCESS CONTROL EQUIPMENT. THE DRAWINGS DO NOT APPEAR TO | | | ILLUSTRATE EQUIPMENT. PLEASE CLARIFY AND PROVIDE | | | INFORMATION IF APPLICABLE. IF EQUIPMENT IS PART OF THE | | | SCOPE OF WORK, SEPARATE SHOP DRAWINGS AND PERMIT IS | | | REQUIRED. | | | | | | 2) PLEASE PROVIDE THE ACTUAL LANGUAGE WITH REGARD TO | | | THE VOICE EVACUATION SYSTEM. | | | | | | 3) IS THERE ANY EXISTING SMOKE MANAGEMENT SYSTEM IN | | | THIS BUILDING? | | | | | | 4) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL | | | STATION SERVICE. THE CERTIFICATE OR COPY OF SUCH WILL | | | BE REQUIRED AT THE TIME OF TO THE FINAL INSPECTION. | | | | | | 5) THE WORD SURVIVABILITY IS USED IN THIS SUBMITTAL. | | | PLEASE VERIFY IF THE FIRE ALARM SYSTEM MEETS THE | | | SURVIVABILITY REQUIREMENTS OF NFPA 72. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|