| Plan Review Notes For Permit 08040226 |
| Permit Number |
08040226 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-06-12 08:34:05 | | | | | | | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS | | | AMENDED, CHAPTER 1.AND FORUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW. | | | | | | 5} INDICATE WHAT THE LOAD CALCULATIONS ARE FOR. IS | | | THERE A NEW SERVICE IN THE SCOPE OF THIS APPLICATION? | | | CHANGE THE DESCRIPTION ON THE APPLICATION TO INDICATE | | | THE SCOPE OF WORK PROPOSED, THERE IS NO MENTION OF | | | ELECTRICAL WORK ON THE APPLICATION.*** THE DESCRIPTION | | | OF WORK REMAINS THE SAME, NO ELECTRICAL WORK | | | INDICATEDON THE APPLICATION.INDICATE IF THE WORK SHOWN | | | NEW OR EXISTING OR BOTH. | | | | | | 6} PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT | | | PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, | | | 106.3.5.4 FBC AS AMENDED** PANEL SCHEDULES HAVE BEEN | | | SUBMITTED, INDICATE WHICH PANEL IS FOR WHICH UNIT(S). | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|