2008-06-12 08:34:05 
  
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FORUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW.
  
 5} INDICATE WHAT THE LOAD CALCULATIONS ARE FOR. IS
 THERE A NEW SERVICE IN THE SCOPE OF THIS APPLICATION?
 CHANGE THE DESCRIPTION ON THE APPLICATION TO INDICATE
 THE SCOPE OF WORK PROPOSED, THERE IS NO MENTION OF
 ELECTRICAL WORK ON THE APPLICATION.*** THE DESCRIPTION
 OF WORK REMAINS THE SAME, NO ELECTRICAL WORK
 INDICATEDON THE APPLICATION.INDICATE IF THE WORK SHOWN
 NEW OR EXISTING OR BOTH.
  
 6} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED** PANEL SCHEDULES HAVE BEEN
 SUBMITTED, INDICATE WHICH PANEL IS FOR WHICH UNIT(S).
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER