| 2008-04-11 11:55:11 | |
| | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS |
| | AMENDED, CHAPTER 1.AND FORUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER |
| | 106.1.3.FBC. |
| | |
| | 2} BOTH ELECTRICAL SHEETS ARE NUMBERED E-14 OF 5. |
| | INDICATE WHICH BUILDING AND UNIT, UPPER OR LOWER, THE |
| | SHEET IS SUPPOSED TO DEPICT. |
| | |
| | 3} GFI'S ARE REQUIRED IN THE KITCHEN FOR COUNTERTOPS |
| | PER 210.8(A)(6). |
| | |
| | 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| | SHALL BE INTERCONNECTED AND HARD WIRED. |
| | |
| | 5} INDICATE WHAT THE LOAD CALCULATIONS ARE FO. IS THERE |
| | A NEW SERVICE IN THE SCOPE OF THIS APPLICATION? CHANGE |
| | THE DESCRIPTION ON THE APPLICATION TO INDICATE THE |
| | SCOPE OF WORK PROPOSED, THERE IS NO MENTION OF |
| | ELECTRICAL WORK ON THE APPLICATION. |
| | |
| | 6} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT |
| | PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, |
| | 106.3.5.4 FBC AS AMENDED. |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |